Toshiba VFNC3-2001P Instruction Manual page 168

Industrial inverter
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
Settings for run/stop via communication
 Command mode selection
Settings for speed command via communication

Communication function parameters (2-wire RS485 communication)
Communication speed, parity, inverter number, and communication error trip time settings can be changed
via panel operations or communication.

6



 Communication time-out action



 Block write data 2
Title
Function
Title
Function
Frequency setting mode
selection
Title
Function
Baud rate
Parity
Inverter number
Communication time-out time
Communication time-out
detection condition
Selection of communication
protocol
Block write data 1
Adjustment
range
 ~ 
Adjustment
range
 ~ 
 (Setting dial)
Adjustment range
3: 9600bps
4: 19200bps
5: 38400bps
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
0-247
0: Desabled (*)
1-100 (s)
0: Alarm only
1: Trip (coast stop)
2: Trip (slowdown stop)
0: Always
1: When  or  is
selected for communication
2: 1 + during operation
0: Toshiba inverter protocol
1: ModbusRTU protocol
0: No selection
1: Command information
2: -
3: Frequency setting value
4: Output data on the terminal
board
5: Analog output for
communication
F-64
E6581595
Standard
Setting example
defaults
 (RS485
 (panel)
communications)
Standard
Setting example
defaults
 (RS485
communications)
Default setting
4
1
0
0.0
0
1
0
0
0