Settings for run/stop via communication
Command mode selection
Settings for speed command via communication
Communication function parameters (2-wire RS485 communication)
Communication speed, parity, inverter number, and communication error trip time settings can be changed
via panel operations or communication.
6
Communication time-out action
Block write data 2
Title
Function
Title
Function
Frequency setting mode
selection
Title
Function
Baud rate
Parity
Inverter number
Communication time-out time
Communication time-out
detection condition
Selection of communication
protocol
Block write data 1
Adjustment
range
~
Adjustment
range
~
(Setting dial)
Adjustment range
3: 9600bps
4: 19200bps
5: 38400bps
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
0-247
0: Desabled (*)
1-100 (s)
0: Alarm only
1: Trip (coast stop)
2: Trip (slowdown stop)
0: Always
1: When or is
selected for communication
2: 1 + during operation
0: Toshiba inverter protocol
1: ModbusRTU protocol
0: No selection
1: Command information
2: -
3: Frequency setting value
4: Output data on the terminal
board
5: Analog output for
communication
F-64
E6581595
Standard
Setting example
defaults
(RS485
(panel)
communications)
Standard
Setting example
defaults
(RS485
communications)
Default setting
4
1
0
0.0
0
1
0
0
0