Toshiba VFNC3-2001P Instruction Manual page 185

Industrial inverter
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
7.3.3
Settings depending on voltage (0 to 5 V) input
<external potentiometer>
You can set the frequency by connecting the FRH kit (optional), or a potentiometer (1 to 10 kΩ – 1/4 W) to the VI
terminal.
Connect the potentiometer between the P5, VI, and CC terminals. The standard voltage for the P5 terminal is 5 V dc.
Instead of using the potentiometer, you can set the frequency settings by inputting an analog voltage signal of 0
to 5 V dc between the VI and CC terminals.
The following shows examples when the run command is input from the terminal.
Title
Function
 Command mode selection
Frequency setting mode

selection
Analog/logic input selection

(VI terminal)
 VI input point 1 setting
 VI input point 1 frequency
 VI input point 2 setting
 VI input point 2 frequency
 Analog input filter
*Depends upon the setup menu settings. Either 50.0 or 60.0 is selected.
MCCB
Power
Supply
* Connect a single-phase
input model to R/L1 and
S/L2/N.
 = : Voltage signal input (0 – 5V)
Adjustment range
0 - 2
0 - 5
0: Voltage signal input (0 - 10 V)
1: Current signal input (4 - 20 mA)
2: Logic input
3: Voltage signal input (0 - 5 V)
0 - 100%
0.0 - 400.0Hz
0 - 100%
0.0 - 400.0Hz
4 - 1000 ms
U/T1
R/L1
VF-nC3
V/T2
S/L2
W/T3
T/L3
S1
S2
FLA
FLB
FLC
F
R
P24
FM
OUT
NO
CC
CC
VI
P5
1 to 10 kΩ - 1/4 W
G-13
Standard
defaults
1
(panel keypad)
2
(setting dial)
0
0
0.0
100
*
64
Run and stop settings
You can switch between forward run (F)
Motor
and reverser run (R), and run/stop with
IM
external signals.
Setting characteristics for the
frequency setting signal and operation
frequency
Set characteristics at two points in the
diagram below.
Connecting and calibrating the
frequency meter
Forward
Select the type of meter connected at
run
 and calibrate.
⇒ For details, see 3.4.
Reverse
run
Hz

Point 1


0%
(0 V
E6581595
Setting example
0
(terminal board)
0
(terminal board VI)
3
(Voltage signal
(0 - 5 V))
0
0.0
100
60.0
64
Point 2
%

100%
to
5 V)
Frequency setting signal