Note 4) During 3 wire operation, sending the jog run mode command stops operation.
Note 5) Be aware that DC braking continues even if a startup signal is input during DC braking.
Note 6) Only F and R maintain HD (operation hold). When using F or R in combination with other
functions, be aware that the other functions do not hold. For example, when F and SS1 are
assigned, F holds, but SS1 does not.
[Parameter settings]
Terminal symbol
S2

Usage example 2 ··· Jog run
Jog run is used for inching the motor. When a jog run signal is input, a jog run frequency is immediately output,
regardless of the acceleration time set.
Assign the jog run function to any input terminal. For example, when assigned to the S2 terminal, set  =
. Jog run is done while the jog input terminal (S2 terminal) and either F or R are ON.
Setting frequency
ST command
F command
R command
S2 command
(
f
Normal operation of
frequency setting signal
input
● The jog frequency is fixed at 5 Hz.
● The stop pattern is slowdown stop.
● The jog run setting terminal is valid when the operation frequency is less than the jog frequency. Jog run does
not function when the operation frequency is higher than the jog frequency.
● Even if an operation command is input midway, jog operation is prioritized.
● The jog frequency is not limited by the upper limit frequency (parameter ).
Title
Function
Input terminal selection 4A (S2)
Forward run Forward run
0
=
)
G-5
Adjustment range
0 ∼ 201
Forward run
Reverse run
E6581595
Setting example
50
(HD operation hold)
7