6.2.2
 : VI terminal function selection
• Function
Parameter setting

Resolution is maximum 1/1000 when VI terminal is used as analog input terminal ( = ).
*
*
6
Changing the functions of VI terminal
This parameter allows you to choose between analog input and logic input for the VI terminal.
Title
Function
Analog/logic input
selection (VI terminal)
In sink logic connection, be sure to insert a resistor between the P24 terminal and the VI terminal, when
using it as the logic input terminal. For details, see 2.3.2 (page B-10).
For information about the interface with the programmable controller, see 7.2.1 (page G-3).
Adjustment range
0: Voltage signal input (0 - 10 V)
1: Current signal input (4 - 20 mA)
2: Logic input
3: Voltage signal input (0 - 5 V)
F-6
E6581595
Default setting
0