Mount the meter in a location and orientation that satisfies the following conditions:
1.6 

Power requirements

Universal (self-switching) AC/DC input, automatically recognizes supply voltage:
18VDC to 100VDC
85VAC (RMS) to 250VAC (RMS)
One pair of wiring terminals accepts either AC or DC power
One internal ground lug for power-supply ground wiring
Maximum load conditions:
Note
For DC power:
Power requirements assume a single transmitter per cable.
At start-up for in-rush current, the power source must provide a minimum of 2.0 amps
of short-term current (1 ms) per transmitter and not pull voltage below 18 VDC.
Length and conductor diameter of the power cable must be sized to provide 18 VDC
minimum at the power terminals, at a load current of 0.2 amps.
Cable sizing formula
M = 18V + (R x L x 0.2A)
M: minimum supply voltage
R: cable resistance
L: cable length (in Ω/ft)
Typical power cable resistance at 68 °F (20.0 °C)
Wire gauge
14 AWG
16 AWG
18 AWG
20 AWG
2.5 mm
1.5 mm
1.0 mm
0.75 mm
0.50 mm
Installation Manual
Allows sufficient clearance to open the transmitter housing cover. Install with 8–10
inches (200–250 mm) clearance at the wiring access points.
Provides clear access for installing cabling to the transmitter.
Provides clear access to all wiring terminals for troubleshooting.
4700 4-Wire: 3.54W (Maximum)
4700 9-Wire: 2.76W (Maximum)
2
2
2
2
2
Resistance
0.0050 Ω/ft
0.0080 Ω/ft
0.0128 Ω/ft
0.0204 Ω/ft
0.0136 Ω/m
0.0228 Ω/m
0.0340 Ω/m
0.0460 Ω/m
0.0680 Ω/m
Planning