Quick Start Guide
00825-0100-4088, Rev CA
April 2019
Rosemount
4088A MultiVariable
Transmitter
®
with Modbus
Output Protocol

Advertisement

loading

Summary of Contents for Emerson Rosemount MultiVariable 4088A

  • Page 1 Quick Start Guide 00825-0100-4088, Rev CA April 2019 ™ ™ Rosemount 4088A MultiVariable Transmitter ® with Modbus Output Protocol...
  • Page 2: Table Of Contents

    Reference Manual for more instruction. All documents are available electronically at Emerson.com/Rosemount. Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operation. Information that raises potential safety issues is indicated with a warning symbol ( ).
  • Page 3: Steps Required For Quick Installation

    April 2019 Quick Start Guide Steps required for quick installation • Start > • Mount the transmitter: Mount the Transmitter • Consider housing rotation: Consider Housing Rotation • Set the switches: Set the Switches • Wiring and power up : Wiring and Power Up •...
  • Page 4: Mount The Transmitter

    Quick Start Guide April 2019 Mount the transmitter Liquid flow applications Procedure 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward. A.
  • Page 5 April 2019 Quick Start Guide Steam flow applications Procedure 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Fill impulse lines with water. A. Direction of flow Mounting brackets Figure 2-1: Mounting Bracket – Coplanar Flange Panel mount Pipe mount Quick Start Guide...
  • Page 6 Only ™ use bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 2-4 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
  • Page 7 Table 2-1 . If bolt material is not shown in Table 2-1, contact the local Emerson representative for more information. Use the following bolt installation procedure: Procedure 1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation.
  • Page 8 Quick Start Guide April 2019 5. Verify the flange bolts are protruding through the sensor module before applying pressure (see Figure 2-5). Example Table 2-1: Torque Values for the Flange and Flange Adapter Bolts Bolt material Head markings Initial torque Final torque Carbon Steel 300 in-lb...
  • Page 9 April 2019 Quick Start Guide O-rings with flange adapters WARNING Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. Only use the O-ring that is designed for its specific flange adapter. A.
  • Page 10 Quick Start Guide April 2019 Figure 2-6: In-line Gage Transmitter A. Low side pressure port (under neck label) Rosemount 4088A MultiVariable Transmitter Quick Start Guide...
  • Page 11: Consider Housing Rotation

    April 2019 Quick Start Guide Consider housing rotation To improve field access to wiring or to better view the optional LCD display: Procedure 1. Loosen the housing rotation set screw. 2. Turn the housing up to 180° left or right of its original (as shipped) position.
  • Page 12 Quick Start Guide April 2019 2. Required: Remove the transmitter cover on the electronics board side (opposite the field terminals side). Do not remove instrument covers in explosive environments when circuit is live. 3. Engage the four-pin connector into the electronics board and snap LCD display into place.
  • Page 13: Set The Switches

    April 2019 Quick Start Guide Set the switches Procedure 1. If the transmitter is installed, secure the bus and remove power. 2. Required: Remove the transmitter cover opposite the field terminal side. Do not remove the instrument covers in explosive environments when the circuit is live.
  • Page 14: Wiring And Power Up

    Quick Start Guide April 2019 Wiring and power up Use the following steps to wire the transmitter: Procedure 1. Remove the cover on the field terminals side of the housing. 2. Set up based on optional process temperature input. a) If the optional process temperature input is being utilized, follow the procedure Install optional process temperature input (Pt 100 RTD...
  • Page 15 April 2019 Quick Start Guide Note The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration. 6. Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion-proof requirements.
  • Page 16 Quick Start Guide April 2019 Figure 5-2: Signal Ground Wiring A. Positive B. Minimize distance C. Trim shield and insulate D. Insulate shield E. Connect shield back to the power supply F. Negative Transmitter case Always ground the transmitter case in accordance with national and local electrical codes.
  • Page 17 April 2019 Quick Start Guide Figure 5-3: Internal Ground Connection A. Ground lug External ground connection The external ground connection is on the outside of the sensor module housing. The connection is identified by a ground symbol ( ). An external ground assembly is included with the option codes shown in Table 5-1 or is...
  • Page 18 Quick Start Guide April 2019 Table 5-1: External Ground Screw Approval Option Codes Option code Description ATEX Flameproof ATEX Intrinsic Safety ATEX Type n ATEX Dust ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E1, I1, N1, and ND) IECEx Flameproof, Dust Ignition-proof IECEx Type n IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, and...
  • Page 19 April 2019 Quick Start Guide case. Do not run transient protection ground wire with signal wiring; the ground wire may carry excessive current if a lightning strike occurs. Install optional process temperature input (Pt 100 RTD Sensor) Note To meet ATEX/IECEx Flameproof certification, only ATEX/IECEx Flameproof cables (temperature input code C30, C32, C33, or C34) may be used.
  • Page 20 Quick Start Guide April 2019 Figure 5-5: Transmitter RTD Wiring Connection 3-wire 4-wire White White A. Ground Lug B. Pt 100 RTD sensor C. Connection head Rosemount 4088A MultiVariable Transmitter Quick Start Guide...
  • Page 21: Verify Device Configuration

    April 2019 Quick Start Guide Verify device configuration For Rosemount 4088A, use Rosemount Transmitter Interface Software with the Rosemount 4088 DTM or a HART Field Communicator with the Rosemount 4088 Device Descriptor to communicate with and verify configuration of the transmitter. Figure 6-1 shows the wiring connections necessary to power a Rosemount 4088 MultiVariable Transmitter and enable communications with a PC-...
  • Page 22 Quick Start Guide April 2019 Figure 6-2: Transmitter Configuration via RS-485 Network Port A. RS- 485 (A) B. RS-485 (B) C. RS-485 bus, twisted pair required D. Bus Termination: AC termination on Rosemount 4088 (see Set the switches) or 120 Ω resistor E.
  • Page 23 April 2019 Quick Start Guide Table 6-1: Field Communication Fast Keys (continued) Category Function Sequence Device Device Status 1, 1 Device Baud Rate 2, 2, 6, 1, 2 Device Turnaround Delay 2, 2, 6, 1, 3 Device 2, 2, 7, 1, 1 Device Long Tag 2, 2, 7, 1, 2...
  • Page 24 Quick Start Guide April 2019 Table 6-1: Field Communication Fast Keys (continued) Category Function Sequence SP Sensor Upper Alert Limit 2, 2, 2, 6, 3 SP Sensor Lower Alert Limit 2, 2, 2, 6, 4 Rosemount 4088A MultiVariable Transmitter Quick Start Guide...
  • Page 25: Trim The Transmitter

    April 2019 Quick Start Guide Trim the transmitter Transmitters are shipped fully calibrated per request or by the factory default of full scale. Use RTIS with the Rosemount 4088 DTM or a HART Field Communicator with the Rosemount 4088 Device Descriptor to communicate with and perform maintenance on the Rosemount 4088 MultiVariable Transmitter.
  • Page 26 Quick Start Guide April 2019 Field Communicator 3, 4, 1, 8, 5 6. Follow the zero DP trim procedure. Rosemount 4088A MultiVariable Transmitter Quick Start Guide...
  • Page 27: Product Certifications

    A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount Ordinary Location Certification As standard, the transmitter has been examined and tested to determine...
  • Page 28 Quick Start Guide April 2019 Installing Equipment in North America ® The US National Electrical Code (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class.
  • Page 29 April 2019 Quick Start Guide 6. Display glass shall be positioned in such a way as to minimize the risk of mechanical impact. I5 FM Intrinsic Safety (IS) and Nonincendive (NI) Certificate FM17US0263X Standards FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004, FM Class 3810 - 2005, ANSI/NEMA 250 - 1991, ANSI/ISA 60529 - 2004, ANSI/ISA 61010-1 - 2004 Markings...
  • Page 30 Quick Start Guide April 2019 Markings Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G; Class III; Class I, Division 2, Groups A, B, C, D; Temp Code T5; seal not required; when installed per Rosemount Drawing 04088-1053;...
  • Page 31 April 2019 Quick Start Guide • T4 for –50 ≤ T ≤ 80 °C with T process = –50 to 120 °C • T5 for –50 ≤ T ≤ 80 °C with T process = –50 to 80 °C • T6 for –50 ≤...
  • Page 32 Quick Start Guide April 2019 Special Conditions for Safe Use (X): 1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66/68. 2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66/68.
  • Page 33 April 2019 Quick Start Guide The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime. 2. Flameproof joints are not intended for repair. 3. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C greater than the maximum specified temperature for location where installed.
  • Page 34 Quick Start Guide April 2019 2. The Rosemount 4088 MV enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 area.
  • Page 35 April 2019 Quick Start Guide Standards ABNT NBR IEC60079-0:2013, ABNT NBR IEC60079-1:2016, ABNT NBR IEC60079-26:2016 Markings Ex db IIC T6…T4 Ga/Gb, T6(–50 ≤ T ≤ +65 °C), T5/T4(–50 ≤ T ≤ +80 °C) Special Conditions for Safe Use (X): 1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected.
  • Page 36 Quick Start Guide April 2019 Supply Modbus Capacitance C Inductance L Special Conditions for Safe Use (X): 1. If the equipment is fitted with an optional 90V transient suppressor, it is not capable of withstanding the 500 V insulation test required by ABNT NBR IRC 60079-11.
  • Page 37 April 2019 Quick Start Guide Combination of E5, I5, E6, and I6 Combination of E1, I1, E5, and I5 Combination of E1, I1, E5, I5, E6, and I6 Combination of EM and IM Quick Start Guide...
  • Page 38 Quick Start Guide April 2019 8.11 EU Declaration of Conformity Rosemount 4088A MultiVariable Transmitter Quick Start Guide...
  • Page 39 April 2019 Quick Start Guide Quick Start Guide...
  • Page 40 Quick Start Guide April 2019 Rosemount 4088A MultiVariable Transmitter Quick Start Guide...
  • Page 41 April 2019 Quick Start Guide Quick Start Guide...
  • Page 42 Quick Start Guide April 2019 Rosemount 4088A MultiVariable Transmitter Quick Start Guide...
  • Page 43 April 2019 Quick Start Guide Quick Start Guide...
  • Page 44 The Emerson logo is a Facebook.com/Rosemount trademark and service mark of Emerson Electric Youtube.com/user/ Co. Rosemount is mark of one of the Emerson RosemountMeasurement family of companies. All other marks are the Google.com/+RosemountMeasurement property of their respective owners.