Variable
Density calibration factors
Function block settings
Channel assignment
L_Type
XD_scale (engineering units
assignment)
2.3

Power requirements

Self-switching AC/DC input, automatically recognizes supply voltage:
85 to 240 VAC, 50/60 Hz, 6 watts typical, 11 watts maximum
18 to 100 VDC, 6 watts typical, 11 watts maximum
Note
For DC power:
Power requirements assume a single transmitter per cable.
At start-up, the power source must provide a minimum of 1.5 amps of short-term
current per transmitter and not pull voltage below 18 VDC.
Length and conductor diameter of the power cable must be sized to provide 18 VDC
minimum at the power terminals, at a load current of 0.7 amps.
Cable sizing formula
M = 18V + (R x L x 0.5A)
M: minimum supply voltage
R: cable resistance (in Ω/ft)
L: cable length (in ft)
Typical power cable resistance at 68 °F (20.0 °C)
Wire gauge
14 AWG
16 AWG
18 AWG
20 AWG
Installation Manual
Setting
D1:
D2:
K1:
K2:
TC:
FD:
Resistance
0.0050 Ω/ft
0.0080 Ω/ft
0.0128 Ω/ft
0.0204 Ω/ft