Parameter : <NR2>, Effective range:0.0 ~ 5.0 (unit: sec)
Parameter returns
[SOURce:]CURRent:INRush:STARt
Function : Set (query) time to start measure inrush current
Example : [SOURce:]CURRent:INRush:STARt?
Parameter : <NR2>, effective range:0.0 ~ 999.9 (unit: msec)
Parameter returns
[SOURce:]CURRent:INRush:INTerval
Function : Set (query) inrush current measurement time
Example : [SOURce:]CURRent:INRush:INTerval?
Parameter : <NR2>, effective range:0.0 ~ 999.9 (unit: msec)
Parameter returns
[SOURce:]FREQuency
Function : Set (query) frequency of output waveform
Example : [SOURce:]FREQuency?
Parameter : <NR2>, effective range:30.0 ~ 1000.0 (unit: Hz)
Parameter returns
[SOURce:]FUNCtion:SHAPe
Function :Set (query) waveform buffer. AC source provides two waveform buffers,
Example :[SOURce:]FUNCtion:SHAPe?
Parameter :A | B
Parameter returns
67
│ www.deltaww.com
:<NR2>
[SOURce:]CURRent:INRush:STARt 200.3
:<NR2>
[SOURce:]CURRent:INRush:INTerval 400.8
:<NR2>
[SOURce:]FREQuency 50.8
:<NR2>
user has to select A or B waveform buffer。
[SOURce:]FUNCtion:SHAPe A
:A | B