Top Vent - Vertical Termination
No Elbows
V
= 60 ft. Max. (18.3 m)
1
Note: If installing a vertical vent/termination off the top of
the appliance, the optional vertical termination baffle may
be needed.
Note: Use SLP Series
components only.
Figure 4.14
Exhaust restrictors are recommended for these verti-
cally terminated products which have excessive draft.
Exhaust restrictors will compensate for high draft, and
restore visual flame height. If the vent configuration has
a total vertical of 15-60 feet, an exhaust restrictor may
be needed. The exhaust restrictor can be located in the
appliance manual bag.
24
Hearth & Home Technologies • DV3732-B, DV3732L-B, DV4236-B Installation Manual • 2496-980 Rev. M • 10/19
V
1
Exhaust restrictor Instructions
1. Install the exhaust restrictor over the center of the ex-
haust outlet in the firebox. See Figure 4.15.
2. Center the exhaust restrictor in the open end of the
exhaust outlet and secure through the slots on the ex-
haust restrictor with the 2-1/4 in. self-tapping screws
provided in the appliance manual bag.
To access the exhaust
openings, remove the
exhaust baffle. To re-
move exhaust baffle, re-
move the two wing nuts.
Top Vent Application
Exhaust restrictor
Rear Vent Application
Exhaust restrictor
Note: Be sure to rein-
stall the exhaust baffle
after exhaust restrictor
installation.
Figure 4.15
EXHAUST BAFFLE