Top Vent - Horizontal Termination - (continued)
Two Elbows
Note: Use SLP Series
components only.
Note: There MUST be a 25% reduction
in total H when using flex vent except
when using the simple up and out
installation. See Figure 4.9.
H
Fire Risk.
• When using SLP-HRC-SS termination cap on top
vented fireplaces, a one foot minimum vertical
vent section is required before installing first
elbow.
Figure 4.12
22
Hearth & Home Technologies • DV3732-B, DV3732L-B, DV4236-B Installation Manual • 2496-980 Rev. M • 10/19
2
INSTALLED
HORIZONTALLY
WARNING**
V
Minimum**
1
90 Elbow Only**
1/2 ft.**
152 mm
1-1/2 ft.**
457 mm
2-1/2 ft.**
762 mm
3-1/2 ft.
1.1 m
4-1/2 ft.
1.4 m
H
+ H
1
2
V
+ H
+ H
1
1
**See Warning Below.
H
1
H
+ H
Maximum
1
2
1/2 ft.
152 mm
1 ft.
305 mm
2 ft.
610 mm
4 ft.
1.2 m
6 ft.
1.8 m
14 ft.
4.3 m
MAX. =14 ft. (4.3 m)
MAX. = 40 ft. (12.2 m)
2
V
1