TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY
240 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
BLOWER
PULLEY
SPEED,
(TURNS
(RPM)
ESP
OPEN)*
208 VOLT AND STANDARD DRIVE
870
6.0**
0.4
900
5.0
0.8
930
4.0
1.1
950
3.0
1.3
980
2.0
1.6
1015
1.0
1.9
208 VOLT AND HIGH SPEED DRIVE
950
6.0
1.3
980
5.0
1.6
1010
4.0
1.8
1020
3.5
1.9
1035
3.0
2.0
1050
2.5
2.1
1075
2.0
2.3
1100
1.0
2.4
230/460/575 VOLT AND STANDARD DRIVE
870
6.0**
0.4
900
5.0
0.8
930
4.0
1.1
950
3.5
1.3
980
2.5
1.6
1015
1.5
1.9
1025
1.0
2.0
230/460/575 VOLT AND HIGH SPEED DRIVE
950
6.0
1.3
980
5.0
1.6
1015
4.0
1.9
1035
3.5
2.0
1050
3.0
2.1
1080
2.0
2.3
1100
1.5
2.4
1120
1.0
2.5
NOTES:
1. Blower performance includes fixed outdoor air, 2" T/A filters, a dry evaporator coil and no electric heat.
2. Refer to Table 13 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
22
6000
7000
BHP
KW
ESP
BHP
2.1
1.8
0.1
2.3
3.2
2.7
0.5
3.5
4.1
3.4
0.9
4.5
4.6
3.9
1.1
5.1
5.3
4.5
1.4
5.8
5.9
5.0
1.7
6.5
4.6
3.9
1.1
5.1
5.3
4.5
1.4
5.8
5.8
4.9
1.7
6.3
6.1
5.1
1.8
6.5
6.2
5.2
1.9
6.8
6.4
5.4
2.0
7.0
6.6
5.5
2.1
7.2
6.7
5.6
2.2
7.3
2.1
1.8
0.1
2.3
3.2
2.7
0.5
3.5
4.1
3.4
0.9
4.5
4.6
3.9
1.1
5.1
5.3
4.5
1.4
5.8
5.9
5.0
1.7
6.5
6.1
5.1
1.8
6.6
4.6
3.9
1.1
5.1
5.3
4.5
1.4
5.8
5.9
5.0
1.7
6.5
6.2
5.2
1.9
6.8
6.4
5.4
2.0
7.0
6.6
5.5
2.1
7.2
6.7
5.6
2.2
7.3
6.8
5.7
2.3
7.4
CFM
8000
KW
ESP
BHP
KW
2.0
-
-
-
2.9
0.2
3.8
3.2
3.8
0.6
4.9
4.1
4.3
0.8
5.5
4.6
4.9
1.2
6.3
5.3
5.5
1.5
7.0
5.9
4.3
0.8
5.5
4.6
4.9
1.2
6.3
5.3
5.3
1.5
6.9
5.8
5.5
1.6
7.1
6.0
5.7
1.7
7.4
6.2
5.9
1.8
7.6
6.4
6.0
1.9
7.8
6.6
6.1
2.1
7.9
6.7
2.0
-
-
-
2.9
0.2
3.8
3.2
3.8
0.6
4.9
4.1
4.3
0.8
5.5
4.6
4.9
1.2
6.3
5.3
5.5
1.5
7.0
5.9
5.6
1.6
7.3
6.1
4.3
0.8
5.5
4.6
4.9
1.2
6.3
5.3
5.5
1.5
7.0
5.9
5.7
1.7
7.4
6.2
5.9
1.8
7.6
6.4
6.0
1.9
7.8
6.6
6.1
2.1
7.9
6.7
6.2
2.2
8.1
6.8
036-21476-002-E-0904
9000
ESP
BHP
KW
ESP
-
-
-
-
-
-
-
-
0.1
5.1
4.3
-
0.4
5.9
5.0
-
0.7
6.9
5.8
0.2
1.0
7.7
6.5
0.6
0.4
5.9
5.0
-
0.7
6.9
5.8
0.2
1.0
7.5
6.3
0.5
1.1
7.8
6.6
0.6
1.2
8.1
6.8
0.7
1.3
8.3
7.0
-
1.5
8.6
7.2
-
-
-
-
-
-
-
-
-
-
-
-
-
0.1
5.1
4.3
-
0.4
5.9
5.0
-
0.7
6.9
5.8
0.2
1.0
7.7
6.5
0.6
1.1
7.9
6.7
0.7
0.4
5.9
5.0
-
0.7
6.9
5.8
0.2
1.0
7.7
6.5
0.6
1.2
8.1
6.8
0.7
1.3
8.3
7.0
-
1.5
8.6
7.2
-
-
-
-
-
-
-
-
-
Unitary Products Group
9400
BHP
KW
-
-
-
-
-
-
-
-
7.3
6.1
8.2
6.9
-
-
7.3
6.1
7.9
6.7
8.3
7.0
8.6
7.3
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.3
6.1
8.2
6.9
8.6
7.3
-
-
7.3
6.1
8.2
6.9
8.6
7.3
-
-
-
-
-
-
-
-