Emerson AMS Trex Device Communicator User Manual page 181

Table of Contents

Advertisement

User Guide
A.2
User Guide
1.800.561.8187
the Trex unit to Poll by Address and ensure the Auto-Connect option in the Field
Communicator Settings is disabled.
Inspect the loop wiring to identify problems. The shield is normally grounded at one end
only, which is usually the control system.
Sample values
Loop Current Flow Minimum voltage for 250 ohms.
mA
4 mA
8 mA
12 mA
16 mA
20 mA
If the voltage across the process-indicating device is greater than the value listed for a
given current flow, the device has at least 250 ohms of internal resistance. If the voltage is
less than the value listed in the table for the given current flow, more resistance needs to
be added to the loop.
If an oscilloscope is available, use it to look for noise on the loop. Use a scope with
differential mode capability or a battery powered/isolated scope to avoid grounding one
side of the loop. Noise with a frequency of 500 Hz to 10,000 Hz is of particular interest, as
this represents frequencies near the HART frequencies of 1200 and 2200 Hz.
Troubleshoot fieldbus communication
Symptom
No communication with the
device.
Unable to change the address
of a device.
www.
Volts
1 Volt
2 Volts
3 Volts
4 Volts
5 Volts
Possible causes
The Trex unit is connected to a
fieldbus segment with a host
system and the device on the
same segment is being
commissioned using the host
system.
An internal fuse may be blown.
The Trex unit is unable to
change the address of a device
that is currently the LAS.
information@itm.com
.com
Troubleshooting
September 2021
Solution
The Trex unit is unable to
communicate with this device
until you go offline and then
back online.
Connect a meter capable of
measuring M ohms to the FF
terminals. An OPEN reading
may indicate a blown fuse.
Establish communication by
putting the Trex unit on the
fieldbus segment first and then
adding one or more devices.
By putting the Trex unit on first,
it remains the LAS and allows
the address change.
181

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents