10 Hand-over to the user

10
Hand-over to the user
Once the test run is finished and the unit operates properly, please
make sure the following is clear for the user:
▪ Fill in the installer setting table (in the operation manual) with the
actual settings.
▪ Make sure that the user has the printed documentation and ask
him/her to keep it for future reference. Inform the user that he can
find the complete documentation at the URL mentioned earlier in
this manual.
▪ Explain the user how to properly operate the system and what to
do in case of problems.
▪ Show the user what to do for the maintenance of the unit.
▪ Explain the user about energy saving tips as described in the
operation manual.
11

Maintenance and service

NOTICE
Maintenance MUST be done by an authorized installer or
service agent.
We recommend performing maintenance at least once a
year. However, applicable legislation might require shorter
maintenance intervals.
NOTICE
In Europe, the greenhouse gas emissions of the total
refrigerant charge in the system (expressed as tonnes CO
equivalent) is used to determine the maintenance intervals.
Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
11.1
Overview: Maintenance and
service
This chapter contains information about:
▪ The yearly maintenance of the outdoor unit
▪ The yearly maintenance of the indoor unit
11.2

Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
NOTICE: Risk of electrostatic discharge
Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.
11.2.1

Opening the indoor unit

CAUTION
The front panel is heavy. Be careful NOT to jam your
fingers when opening or closing the unit.
You just need to remove the front panel of the unit to gain access to
most parts which need maintenance. In rare cases, you may also
need to remove the switch box.
Installer reference guide
78
11.3
Checklist for yearly maintenance
of the outdoor unit
Check the following at least once a year:
▪ Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to
dust, dirt, leaves, etc. It is recommended to clean the heat
exchanger yearly. A blocked heat exchanger can lead to too low
pressure or too high pressure leading to worse performance.
11.4
Checklist for yearly maintenance
of the indoor unit
Check the following at least once a year:
▪ Water pressure
▪ Water filter
▪ Water pressure relief valve
▪ Discharge piping
▪ Pressure relief valve of the domestic hot water tank
▪ Booster heater of the domestic hot water tank
▪ Switch box
▪ Descaling
▪ Chemical disinfection
▪ Anode
▪ Pressure reducing valve of the domestic hot water tank kit
▪ Pressure relief valve of the domestic hot water tank kit
2
Water pressure
Keep water pressure above 1 bar. If it is lower, add water.
Water filter
Clean the water filter.
NOTICE
Handle the water filter with care. Do NOT use excessive
force when you reinsert the water filter so as NOT to
damage the water filter mesh.
1
2
4
5
Water pressure relief valve
Open the valve and check if it operates correctly. The water may be
very hot!
Checkpoints are:
▪ The water flow coming from the relief valve is high enough, no
blockage of the valve or in between piping is suspected.
▪ Dirty water coming out of the relief valve:
▪ open the valve until the discharged water does NOT contain dirt
anymore
▪ flush the system and install an additional water filter (a
magnetic cyclone filter is preferable).
3

ERLQ004~008CA + EHVH04+08SU18+26CB6W

Daikin Altherma – Low temperature split
4P449978-1B – 2018.07