Daikin Altherma EHVH08SU18CB6W Installer's Reference Manual page 59

Low temperature split
Hide thumbs Also See for Altherma EHVH08SU18CB6W:
Table of Contents

Advertisement

NOTICE
▪ When adjusting the leaving water temperature ranges,
all desired leaving water temperatures are also
adjusted to guarantee they are between the limits.
▪ Always balance between the desired leaving water
temperature with the desired room temperature and/or
the capacity (according to the design and selection of
the
heat
emitters).
temperature is the result of several settings (preset
values, shift values, weather dependent curves,
modulation). As a result, too high or too low leaving
water temperatures could occur which lead to
overtemperatures or capacity shortage. By limiting the
leaving water temperature range to adequate values
(depending on the heat emitter), such situations can be
avoided.
Example: Set the minimum leaving water temperature to 28°C to
avoid NOT to be able to heat up the room: leaving water
temperatures
MUST
be
sufficiently
temperatures (in heating).
#
Code
Leaving water temperature range for the main leaving water
temperature zone (= the leaving water temperature zone with the
lowest leaving water temperature in heating operation)
[A.3.1.1.2.2] [9-00]
Maximum temp (heating)
37°C~depending on outdoor unit
(default: 55°C)
[A.3.1.1.2.1] [9-01]
Minimum temp (heating)
15°C~37°C (default: 25°C)
Leaving water temperature range for the additional leaving water
temperature zone (= the leaving water temperature zone with the
highest leaving water temperature in heating operation)
[A.3.1.2.2.2] [9-06]
Maximum temp (heating)
37°C~depending on outdoor unit
(default: 55°C )
[A.3.1.2.2.1] [9-05]
Minimum temp (heating)
15°C~37°C (default: 25°C)
Leaving water temperature overshoot temperature
This function defines how much the water temperature may rise
above the desired leaving water temperature before the compressor
stops. The compressor will startup again when the leaving water
temperature drops below the desired leaving water temperature.
This function is ONLY applicable in heating mode.
#
Code
N/A
[9-04]
1°C~4°C (default: 1°C)
Leaving water temperature compensation around 0°C
In heating operation, the desired leaving water temperature is locally
increased
around
an
outdoor
compensation can be selected when using an absolute or a weather
dependent desired temperature (see illustration below). Use this
setting to compensate for possible heat losses of the building due to
the evaporation of melted ice or snow (e.g. in cold region countries).
ERLQ004~008CA + EHVH04+08SU18+26CB6W
Daikin Altherma – Low temperature split
4P449978-1B – 2018.07
The
desired
leaving
water
higher
than
the
room
Description
Description
temperature
of
0°C.
This
T
T
t
t
L
L
R
R
T
A
0°C
0°C
a
b
a
Absolute desired LWT
b
Weather dependent desired LWT
#
Code
N/A
[D-03]
▪ 0 (disabled) (default)
▪ 1 (enabled) L=2°C,
R=4°C (−2°C<T
▪ 2 (enabled) L=4°C,
R=4°C (−2°C<T
▪ 3 (enabled) L=2°C,
R=8°C (−4°C<T
▪ 4 (enabled) L=4°C,
R=8°C (−4°C<T
Leaving water temperature maximum modulation
ONLY applicable in room thermostat control and when modulation is
enabled. The maximum modulation (=variance) on the desired
leaving water temperature decided on the difference between the
actual and desired room temperature, e.g. 3°C modulation means
the desired leaving water temperature can be increased or lowered
by 3°C. Increasing the modulation results in better performance (less
On/OFF, faster heat up), but note that depending on the heat
emitter, there MUST ALWAYS be a balance (refer to the design and
selection of the heat emitters) between the desired leaving water
temperature and the desired room temperature.
#
Code
N/A
[8-06]
0°C~10°C (default: 3°C)
Temperature ranges (room temperature)
ONLY applicable in room thermostat control. In order to save energy
by preventing overheating the room, you can limit the range of the
room temperature.
NOTICE
When adjusting the room temperature ranges, all desired
room temperatures are also adjusted to guarantee they are
between the limits.
#
Code
Room temp. range
[A.3.2.1.2]
[3-06]
Maximum temp (heating)
18°C~30°C (default: 30°C)
[A.3.2.1.1]
[3-07]
Minimum temp (heating)
12°C~18°C (default: 12°C)
Room temperature step
ONLY applicable in room thermostat control and when the
temperature is displayed in °C.
#
Code
[A.3.2.4]
N/A
Room temp. step
▪ 1°C
temperature on the user interface is
settable per 1°C.
▪ 0.5°C. The desired room temperature
on the user interface is settable per
0.5°C. The actual room temperature is
displayed with an accuracy of 0.1°C.
8 Configuration
T
A
Description
<2°C)
A
<2°C)
A
<4°C)
A
<4°C)
A
Description
Description
Description
(default).
The
desired
room
Installer reference guide
59

Advertisement

Table of Contents
loading

Table of Contents