Daikin Altherma EHVH08SU18CB6W Installer's Reference Manual page 100

Low temperature split
Hide thumbs Also See for Altherma EHVH08SU18CB6W:
Table of Contents

Advertisement

4/8
Field settings table
Breadcrumb
Field code
Setting name
└─ Maximum setpoint
A.4.5
[6-0E]
└─ SP mode
A.4.6
└─ Weather dependent curve
A.4.7
[0-0B]
Weather-dependent curve
A.4.7
[0-0C]
Weather-dependent curve
A.4.7
[0-0D]
Weather-dependent curve
A.4.7
[0-0E]
Weather-dependent curve
└─ Heat sources
└─ Backup heater
A.5.1.1
[4-00]
Operation mode
A.5.1.3
[4-07]
Enable BUH step 2
A.5.1.4
[5-01]
Equilibrium temp.
└─ System operation
└─ Auto restart
A.6.1
[3-00]
└─ Preferential kWh rate
A.6.2.1
[D-00]
Allowed heaters
A.6.2.2
[D-05]
Forced pump OFF
└─ Pwr consumpt. Control
A.6.3.1
[4-08]
Mode
A.6.3.2
[4-09]
Type
A.6.3.3
[5-05]
Amp. value
A.6.3.4
[5-09]
kW value
A.6.3.5.1
[5-05]
Amp. limits for DI
A.6.3.5.2
[5-06]
Amp. limits for DI
A.6.3.5.3
[5-07]
Amp. limits for DI
A.6.3.5.4
[5-08]
Amp. limits for DI
A.6.3.6.1
[5-09]
kW limits for DI
A.6.3.6.2
[5-0A]
kW limits for DI
A.6.3.6.3
[5-0B]
kW limits for DI
A.6.3.6.4
[5-0C]
kW limits for DI
A.6.3.7
[4-01]
Priority
└─ Averaging time
A.6.4
[1-0A]
└─ Ext amb. sensor offset
A.6.5
[2-0B]
└─ Boiler efficiency
A.6.A
[7-05]
└─ Emergency
A.6.C
└─ Overview settings
A.8
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
A.8
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
A.8
[0-02]
High ambient temp. for LWT add zone heating WD curve.
A.8
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
A.8
[0-04]
--
A.8
[0-05]
--
A.8
[0-06]
--
A.8
[0-07]
--
A.8
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
A.8
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
A.8
[0-0D]
High ambient temp. for DHW WD curve.
A.8
[0-0E]
Low ambient temp. for DHW WD curve.
4P449983-1 - 2016.06
Leaving water value for high ambient temp. for
DHW WD curve.
Leaving water value for low ambient temp. for
DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Limit DI1
Limit DI2
Limit DI3
Limit DI4
Limit DI1
Limit DI2
Limit DI3
Limit DI4
Range, step
Default value
R/W
40~65°C, step: 1°C
65°C
R/W
0: Fixed
1: Weather dep.
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
45~[6-0E]°C, step: 1°C
65°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
0~2
0: Disabled
1: Enabled
R/W
0: No
1: Yes
R/W
-15~35°C, step: 1°C
0°C
R/W
0: No
1: Yes
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
R/W
0: Forced off
1: As normal
R/W
0: No limitation
1: Continuous
2: Digital inputs
R/W
0: Current
1: Power
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0: None
1: BSH
2: BUH
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
R/W
0: Manual
1: Automatic
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
R/W
[9-05]~[9-06]°C, step: 1°C
45°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
8
12
35
20
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
45~[6-0E]°C, step: 1°C
65°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
Installer setting at variance with
default value
Date
Value
(*1) *04/08*_(*2) *11/16*