Daikin Altherma EHVH08SU18CB6W Installer's Reference Manual page 52

Low temperature split
Hide thumbs Also See for Altherma EHVH08SU18CB6W:
Table of Contents

Advertisement

8 Configuration
#
Code
[A.2.1.8]
[7-02]
The system can supply leaving water to
up to 2 water temperature zones. During
configuration, the number of water zones
must be set.
Number of LWT zones:
▪ 0 (1 LWT zone)(default): Only 1
leaving water temperature zone. This
zone is called the main leaving water
temperature zone.
▪ a: Main LWT zone
#
Code
[A.2.1.8]
[7-02]
<< continuation
▪ 1 (2 LWT zones): 2 leaving water
temperature zones. The zone with the
lowest leaving water temperature (in
heating) is called the main leaving
water temperature zone. The zone
with
temperature (in heating) is called the
additional leaving water temperature
zone. In practice, the main leaving
water temperature zone consists of
the higher load heat emitters and a
mixing station is installed to achieve
the desired leaving water temperature.
▪ a: Add LWT zone
▪ b: Main LWT zone
Installer reference guide
52
Description
a
continued >>
Description
the
highest
leaving
water
a
b
#
Code
[A.2.1.9]
[F-0D]
When the space heating control is OFF
by the user interface, the pump is always
OFF. When the space heating control is
On, you can select the desired pump
operation mode (only applicable during
space heating)
Pump operation mode:
▪ 0 (Continuous): Continuous pump
operation, regardless of thermo ON or
OFF condition. Remark: continuous
pump operation requires more energy
than
operation.
b
b
▪ a: Space heating control (user
interface)
▪ b: OFF
▪ c: On
▪ d: Pump operation
#
Code
[A.2.1.9]
[F-0D]
<< continuation
▪ 1 (Sample): The pump is ON when
there is heating demand and the
leaving water temperature has NOT
reached the desired temperature yet.
When thermo OFF condition occurs,
the pump runs every 5  minutes to
check the water temperature and
demand
Remark: Sample is NOT available in
external room thermostat control or
room thermostat control.
a
b
d
g
b
▪ a: Space heating control (user
interface)
▪ b: OFF
▪ c: On
▪ d: LWT temperature
▪ e: Actual
▪ f: Desired
▪ g: Pump operation
ERLQ004~008CA + EHVH04+08SU18+26CB6W
Description
sample
or
request
pump
a
c
c
d
continued >>
Description
heating
if
necessary.
c
e
f
c
continued >>
Daikin Altherma – Low temperature split
4P449978-1B – 2018.07