Process interfacing via an automation system (PLC, PC)
9.4 Control with FB 79
or "ERROR" has the value "TRUE". If "ERROR" has the value "TRUE", "ERRCODE" has the
value "DW#16#00010007".
Note
Change of operating state from "Stop" to "Start"
If an error has occurred that changes the optical reader to "Stop", eliminate and
acknowledge the error. You can then return the optical reader to "Start" mode by changing
program (COMMAND = W#16#0001).
9.4.5.2

Parameter overview

Table 9- 44
Overview of FB 79 parameters
Parameter
Declaration
LADDR_
INPUT
STEUER
LADDR_
INPUT
STATUS
LADDR_
INPUT
SEND
LADDR_
INPUT
RECV
COMMAND
INPUT
PARAM1
INPUT
RESET
INPUT
RECV
INPUT
ACTIVE
OUTPUT
142
Data type
Address
(instance DB)
WORD
0.0
WORD
2.0
WORD
4.0
WORD
6.0
WORD
8.0
BYTE
10.0
BOOL
11.0
ANY
12.0
BOOL
22.0
Default
Description
W#16#0000
Address of the control byte of the optical
reader.
The address must be in the process image of
the CPU you are using.
W#16#0000
Address of the status byte of the optical read-
er.
The address must be in the process image of
the CPU you are using.
W#16#0000
Start address of the "Send" user data inter-
face of the optical reader.
W#16#0000
Start address of the "Receive" user data inter-
face of the optical reader.
W#16#0000
Job number:
The permitted values are described following
this table.
B#16#00
Number of the program to be selected (rele-
vant only for jobs "W#16#0001" and
"W#16#0002").
FALSE
Reset pending error and FB initialization.
Receive area for the result string. Only data
block areas and the "BYTE" data type are
permitted.
You must interconnect this parameter and the
data block must be at least as large as the
maximum DMC string that can be expected.
FALSE
ACTIVE = TRUE:
Editing of the last job has not yet completed.
Operating Instructions, 05/2019, C79000-G8976-C494-02