Appendix 1.2 Combinations Of A/D Converter Module Functions And Gx Configurator-Ad Software Versions; Appendix 1.3 Precautions For Replacing The Module Of Function Version A With The One Of Function Version B Or Later - Mitsubishi MELSEC-Q Q Series User Manual

Analog-digital converter module, programmable logic controller, gx configurator-ad sw0d5c-qadu-e
Table of Contents

Advertisement

APPENDIX
Appendix 1.2 Combinations of A/D converter module functions and GX Configurator-AD
software versions
Function
Normal resolution mode
High resolution mode
High resolution mode status flag (X8)
Maximum value/minimum value reset
completed flag (XD)
Multiple PLC system compatibility
Normal mode - offset/gain setting mode
3
switching
Appendix 1.3 Precautions for replacing the module of function version A with the one of
function version B or later
App.
App. - 2
All manuals and user guides at all-guides.com
The following table indicates the A/D converter module functions and corresponding
GX Configurator-AD software versions.
SW0D5C-QADU
-E 00A
1
1
2
1
2
1
1 Functions added by function version B.
2 When the A/D converter module is function version A and the GX Configurator-AD software
version is SW0D5C-QDAU-E 20C or later or GX Configurator-AD Version 1.10L or later,
OFF is always displayed.
3 Functions added by function version C.
(1) Incorporation into an existing system
You can use the wiring designed for function version A as-is to mount the A/D
converter module of function version B or later.
(2) Program utilization
You can use the program created for function version A as-is with the A/D
converter module of function version B or later.
(3) Switch setting for intelligent function module
The setting of the offset/gain setting mode differs between function versions A
and B or later.
Perform the offset/gain settings after checking the RUN LED flashes in
offset/gain setting mode. If the RUN LED does not flash, check to see if the
switch 4 setting is correct.
(Refer to Section 4.5 for the intelligent function module switch setting of function
version B or later.)
<Contents of switch 4 setting for function version A>
H
00
H
01
to FF
H
Software version
SW0D5C-QADU
-E 10B
00
: With temperature drift correction
H
01
to FF
: Without temperature drift correction
H
H
: Normal mode (A/D conversion processing)
: Offset/gain setting mode
H
MELSEC-Q
GX Configurator-
GX Configurator-
AD Version 1.10L
AD Version 1.16S
to 1.15R
or later
: Compatible
: Not compatible
App. - 2

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Melsec-q q64adMelsec-q q68advMelsec-q q68adi