3.4.1 Buffer memory assignment (Q64AD)

This section describes the assignment of the Q64AD buffer memory.
Address
Hexadecimal
Decimal
0
0
A/D conversion enable/disable setting
H
1
1
CH1 Average time/average number of times
H
2
2
CH2 Average time/average number of times
H
3
3
CH3 Average time/average number of times
H
4
4
CH4 Average time/average number of times
H
5
5
H
to
to
8
8
H
9
9
Averaging process setting
H
A
10
A/D conversion completed flag
H
B
11
CH1 Digital output value
H
C
12
CH2 Digital output value
H
D
13
CH3 Digital output value
H
E
14
CH4 Digital output value
H
F
15
H
to
to
12
18
H
13
19
H
14
20
Setting range (CH1 to CH4)
H
15
21
H
16
22
Offset/gain setting mode Offset specification
H
17
23
Offset/gain setting mode Gain specification
H
18
24
H
to
to
1D
29
H
1E
30
CH1 Maximum value
H
1F
31
H
20
32
CH2 Maximum value
H
21
33
H
22
34
CH3 Maximum value
H
23
35
H
24
36
CH4 Maximum value
H
25
37
H
1 Indicates whether reading and writing to/from a sequence program are enabled.
2 Areas used to restore the user range settings offset/gain values when online
3 - 17
All manuals and user guides at all-guides.com
Table 3.4 Buffer memory assignment (Q64AD)
R/W
Description
R/W
R/W
R/W
R/W
R/W
System area
R/W
R
R
R
R
R
System area
Error code
R
R
System area
R/W
R/W
System area
R/W
CH1 Minimum value
R/W
R/W
CH2 Minimum value
R/W
R/W
CH3 Minimum value
R/W
R/W
CH4 Minimum value
R/W
R : Read enabled
W : Write enabled
module change is made.
Refer to chapter 7 for details of online module change.
Address
1
Hexadecimal
Decimal
26
38
H
to
to
9D
157
H
9E
158
H
9F
159
H
A0
160
H
to
to
C7
199
H
Pass data classification setting
C8
200
H
C9
201
H
CH1 Industrial shipment settings offset value
CA
202
H
CH1 Industrial shipment settings gain value
CB
203
H
CH2 Industrial shipment settings offset value
CC
204
H
CH2 Industrial shipment settings gain value
CD
205
H
CH3 Industrial shipment settings offset value
CE
206
H
CH3 Industrial shipment settings gain value
CF
207
H
CH4 Industrial shipment settings offset value
D0
208
H
CH4 Industrial shipment settings gain value
D1
209
H
CH1 User range settings offset value
D2
210
H
CH1 User range settings gain value
D3
211
H
CH2 User range settings offset value
D4
212
H
CH2 User range settings gain value
D5
213
H
CH3 User range settings offset value
D6
214
H
CH3 User range settings gain value
D7
215
H
CH4 User range settings offset value
D8
216
H
CH4 User range settings gain value
D9
217
H
MELSEC-Q
R/W
Description
System area
R/W
Mode switching setting
R/W
System area
2
R/W
System area
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W
2
R/W