Troubleshooting; Error Code List - Mitsubishi MELSEC-Q Q Series User Manual

Analog-digital converter module, programmable logic controller, gx configurator-ad sw0d5c-qadu-e
Table of Contents

Advertisement

8 TROUBLESHOOTING

8 TROUBLESHOOTING

8.1 Error Code List

Error code
(decimal)
The input range is set an illegal value using the
10
intelligent function module switch in GX Developer.
indicates the incorrectly specified channel number.
111
Module error at startup.
The G.OGSTOR instruction was executed in the
1
161
offset/gain setting mode.
• The G.OGSTOR instruction was executed
consecutively.
162
• At the time of offset/gain setting, a set value was
written to the E
The G.OGSTOR instruction was executed for the
163
model that differs from the model for which the
G.OGLOAD instruction had been executed.
The average time setting value for buffer memory
addresses 1 to 8 (Un\G1 to Un\G8) is outside the
20
range of 2 to 5000 ms.
specified channel number.
The average number of times setting value for buffer
memory addresses 1 to 8 (Un\G1 to Un\G8) is
30
outside the range of 4 to 62500 times.
8
the incorrectly specified channel number.
The offset value is equal to or greater than the gain
value at the time of user range setting or user range
40
restoration.
indicates the error causing channel number.
The offset/gain channels were set at the same time
500
during offset and gain value settings, or both were
set to 0.
1: Not written to the buffer memory address 19 (Un\G19). Written to the completion status area (S)+1 of the G.OGSTOR
instruction.
8 - 1
All manuals and user guides at all-guides.com
The following section explains the types of errors that may occur when the A/D
converter module is used, and how to troubleshoot such errors.
If an error occurs in the A/D converter module while writing to or reading data from the
PLC CPU, the applicable error code is written to buffer memory address 19 (Un\G19).
Table 8.1 Error code list
Error description
2
PROM 26 or more times.
indicates the incorrectly
POINT
(1) If more than one error occurs, the error code first detected by the A/D
converter module is stored. No other error codes will be stored.
(2) The error can be cleared by setting the error clear request (YF) to "ON".
(3) The error is cleared at the time of mode switching.
Reset to the correct parameter with GX Developer
parameter setting. (See Section 4.5.)
Turn the power OFF and ON again. If the error
occurs again, the module may be malfunctioning.
Contact the nearest distributor or branch office with
the description of the problem.
Do not execute the G.OGSTOR instruction in the
offset/gain setting mode.
• Execute the G.OGSTOR instruction only once for
one module.
• At the time of offset/gain setting, write a set value
only once at one time.
Execute the G.OGLOAD and G.OGSTOR
instructions for the same model.
Reset the average time setting to a value within the
range of 2 to 5000 ms.
Reset the average number of times setting value to
indicates
within the range of 4 to 62500 times.
Reset so that the offset value becomes smaller than
the gain value.
Reset the contents of buffer memory addresses 22
and 23 (Un\G22 and Un\G23).
MELSEC-Q
Processing
8 - 1