Download Print this page

Electrical Installation - Omron JZA24P0BAA Quick Start Manual

Compact general purpose inverter, 200/400 v class three-phase input 0.1/0.2 to 0.4/1.5/4.0 kw

Advertisement

3

Electrical Installation

The figure below shows the main and control circuit wiring.
Terminals marked -,+1,+2,B1,B2 are for
connecting an option. Do not wire AC
power lines to these terminals.
For 1-phase
power supply use
R/L1 and S/L2
Fuses
L1
Power
L2
Supply
L3
Main
Switch
Forward/Stop
Reverse/Stop
External Fault
Fault Reset
Multi-speed 1
Multi-function
digital inputs
(default setting)
Analog input
I80E-EN
J1000 Quick Start Guide
DC reactor
(option)
Link
+2
R/L1
S/L2
Filter
T/L3
S1
S2
S3
S4
S5
DIP
switch S3
SC
Shielded ground
terminal
Analog input power supply
+V
2 kΩ
+10.5 Vdc, max. 20 mA
A1
Analog input
0 to 10 V (20 kΩ) or
0/4 to 20 mA (250 kΩ)
AC
Symbols:
Use twisted pair cables
Use shielded twisted pair cables
Braking
Thermal
relay
resistor
(option)
-
+1
B1
B2
U/T1
J1000
V/T2
W/T3
Option unit
connector
DIP switch S1
+24 V 8 mA
I
V
MA
MB
+24 V
MC
SINK
SOURCE
AM
AC
Indicates a main circuit terminal
Indicates a control circuit terminal.
3 Electrical Installation
U
V
W
Shielded
Cable
Ground
Multi-function relay output
250 Vac / 30 Vdc (10 mA to 1A)
Fault
(default setting)
Analog output
0 to +10 Vdc (2mA)
(Output frequency)
M
Monitor output
(default setting)
11

Advertisement

loading

This manual is also suitable for:

JzaJ1000Jzab0p1baa