5 Start Up
Analog Monitor Output (H4-
Use the H4-
parameters to set up the output value of the analog monitor output and to
adjust the output voltage levels. The default monitor value setting is "Output frequency".
Frequency Reference and Acceleration/ Deceleration Times
Frequency Reference Setup(b1-01)
Set parameter b1-01 according to the frequency reference used.
b1-01
Reference source
0
Operator keypad
1
Analog input
Serial
Communica-
2
tions Option
3
Potentiometer Option Potentiometer Option
Acceleration/ Deceleration Times and S-Curves
There are two sets of acceleration and deceleration times which can be set in the C1-
parameters. The default activated accel/ decel times are C1-01/02. Adjust these times to the
appropriate values required by the application. If necessary S-curves can be activated in the
C2-
parameters for softer accel/ decel start and end.
Test Run
Perform the following steps to start up the machine after all parameter settings have been
done.
1. Run the motor without load and check if all input, outputs and the sequence work as
desired.
2. Connect the load to the motor.
3. Run the motor with load and make sure that there is no vibrations, hunting or motor
stalling occurs.
After taking the steps listed above, the drive should be ready to run the application and per-
form the basic functions. For details about more advanced setup refer to the technical man-
ual.
20
)
Set the frequency references in the d1-
switch over between different reference values.
Apply the frequency reference signal to terminal A1.
RS232C or RS422/485 Memobus communication
Frequency reference input
parameters and used digital inputs to
I80E-EN
J1000 Quick Start Guide