Compact general purpose inverter, 200/400 v class three-phase input 0.1/0.2 to 0.4/1.5/4.0 kw

Advertisement

LED Display ALM FLT
Heatsink
Overheat
or
Motor
Overload
Drive
Overload
DC
Overvoltage
Input Phase
Loss
DC
Undervoltage
or
DC Charge
Circuit Fault
I80E-EN
J1000 Quick Start Guide
• Surrounding temperature is too high.
• The cooling fan has stopped.
• The heatsink is dirty.
• The airflow to the heatsink is restricted.
• The motor load is too heavy.
• The motor is operated at low speed with heavy load.
• Cycle times of accel./ decel. are too short.
• Incorrect motor rated current has been set.
• The load is too heavy.
• The drive capacity is too small.
• Too much torque at low speed.
DC bus voltage rose too high.
• The deceleration time is too short.
• Stall prevention is disabled.
• Braking chopper/ resistor broken
• Too high input voltage.
• Input voltage drop or phase imbalance.
• One of the input phase is lost.
• Loose wires at the drive input.
The voltage in the DC bus fell below the undervoltage detection level.
• The power supply failed or one input phase has been lost.
• The power supply is too weak.
The charge circuit for the DC bus is broken.
7 Troubleshooting