USER GUIDE
Parameter
P18
first hard timed chill step duration
P19
compressor delay from device power on
(from restoration of power)
P20
minimum elapsed time period between
two consecutive compressor start-up
operations
P21
minimum compressor shut-down time
P22
defrost type
0 = electric (defrost on relay)
1 = hot gas (defrost compressor and
relay on)
2 = air (evaporator fan on)
P23
defrost end temperature (with reference
to the evaporator probe)
P24
maximum defrost duration
P25
defrost interval during storage; see
also P26
0 = intermittent defrosting will never
be activated (only the first will be
activated)
P26
first defrost delay from start of storage;
see also P25
P27
defrosting at start of chilling and
freezing 1 = YES
P28
drip-drain duration
P29
resetting of compressor protections at
start of defrosting (only if P22 = 1)
1 = YES
P30
elapsed time between the defrost
request and switching on the
compressor (only if P22 = 1 and
providing that the compressor is off
when the defrost is requested); see P31
(7) (8) also
P31
elapsed time between the defrost
request and activation of the solenoid
valve (only if P22 = 1 and on condition
that the compressor is off when
defrosting is requested); see also P30
P32
temperature above which the
evaporator fan is switched off during
storage (with reference to the
evaporator probe)
P33
P32 differential
P34
evaporator fan activity during defrosting
(only if P22 = 0 or 1)
0 = on
1 = off
P35
evaporator stop time after dripping
P36
temperature above which the
evaporator fan is switched off (with
reference to the cabinet probe)
P37
effect caused by activation of microport
input on evaporator fan
0 = no effect
1 = the evaporator fan will be switched
off
P38
microport input contact type
0 = NA (input active with contact
closed)
1 = NC (input active with contact open)
P39
micro port input alarm delay
System Diagnosis Guide
Description
Factory
Value
45
0
0
0
2
8
10
6
1
0
2
0
30
0
3
1
0
3
90
1
1
0
Parameter
P40
high pressure input contact type
0 = NA (input active with contact
closed)
1 = NC (input active with contact open)
P41
high pressure input alarm delay
P42
low pressure input contact type
0 = NA (input active with contact
closed)
1 = NC (input active with contact open)
P43
low pressure input alarm delay
P44
compressor thermal protection input
contact type
0 = NA (input active with contact
closed)
1 = NC (input active with contact open)
P45
compressor thermal protection input
alarm delay
P46
UV light on duration (duration of cabinet
sterilisation)
P47
needle probe heating end temperature
(with reference to the needle probe)
P48
maximum duration of needle probe
heating
P49
the temperature, below which the
door elements are switched on (with
reference to the cabinet probe)
P50
P49 differential
P51
condenser fan activity in the absence of
the condenser probe (P61 = 0)
0 = in parallel with compressor
1 = on
P52
the temperature below which the
condenser fan is switched off in the
presence of the condenser probe
(P61 = 1) and on condition that the
compressor is on (with reference to the
condenser probe); see also P54
P53
P52 differential
P54
condenser fan switch off delay on
switching off the compressor in the
presence of the condenser probe
(P61 = 1); see also P52
P55
chill and freeze cycle completion buzzer
duration
P56
maximum buzzer duration during an
alarm state
P57
elapsed time between switching on
the compressor and pump down valve
activation (pump down in power up);
also elapsed time between deactivation
of the pump down valve and switching
off the compressor (pump down in
power down)
P58
defrost parameter units of
measurement
0 = P25 h, P24, P26, P28, and P35 min
1 = P25 min, P24, P26, P28, and P35 s
P59
reserved
P60
probe type
0 = NTC
1 = PTC
P61
condenser probe enabling 1 = YES
54
Description
Factory
Value
0
120
0
0
0
0
5
45
15
5
2
1
20
5
30
3
15
10
0
0
0
0