Nortel CS 1000M HG Manual page 47

Fiber remote multi-ipe interface fundamentals
Table of Contents

Advertisement

Interface to the local system and the Remote IPE and connect the fiber-optic
link between the local and remote Fiber Remote Multi-IPE Interface units.
However, if the Superloop Network card is not installed, install it now.
Installing the Superloop Network card
The purpose of the following steps is to describe how and where to install
the Superloop Network card(s). In a new system, the cards would have
been installed in network card slots at the factory; however, it may be
necessary to install additional Superloop Network cards to expand the
number of remote sites or replace a defective card.
To install the Superloop Network card(s), follow the steps in
"Installing the Superloop Network card" (page
Procedure 1
Installing the Superloop Network card
Step
1
2
3
4
5
Copyright © 2007, Nortel Networks
.
Action
Set the ENB/DIS switch on the Superloop Network card to DIS.
Pull the Superloop Network card's upper and lower locking device
away from the faceplate.
While holding the card by these locking devices, insert it into the
card guides of the selected network card slot.
Slide the card into the module until it engages the backplane
connector.
Carefully push the upper and lower locking device levers towards the
faceplate to insert the card connector into the backplane connector
and lock the card in place.
Set the ENB/DIS switch on the Superloop Network card to ENB and
observe the LED on the card as it performs self-tests.
The LED should blink three times and then stay ON until enabled
by software.
When enabled by software, the LED turns OFF permanently, if
operational.
Nortel Communication Server 1000
Fiber Remote Multi-IPE Interface Fundamentals
NN43021-556 01.01 Standard
Release 5.0 30 May 2007
Fiber-optic equipment installation 47
47).
—End—