Menus And Submenus - Johnson Controls TEC3322-1 Series Installation Manual

Networked and wireless proportional fan coil and individual zone thermostat controllers with dehumidification capability
Hide thumbs Also See for TEC3322-1 Series:
Table of Contents

Advertisement

Supply Fan Runtime—The TEC3000 supports setting runtime limits on the supply fan command. When the
limit is exceeded, an alarm turns on. This feature is intended to be used as a maintenance reminder. Setting
the runtime limit to 0 disables this feature.
Supply Air Temperature Diagnostics—The TEC3000 supports diagnostics when you have a Supply Air
Temperature installed. The TEC3000 monitors the supply air. If you call for cooling or heating and the
temperature does not fall or rise by at least the supply air temperature alarm offset value within the supply air
temperature alarm delay, an alarm is generated. If the monitoring occurs while cooling, a cooling ineffective
alarm is generated. If the monitoring occurs while heating, a heating ineffective alarm is generated. If you set
the supply air temperature offset value set to 0, this alarm is disabled.
Zone Temperature Alarm—When enabled, the user can set a low and high temperature alarm; and if the zone
temperature rises or falls below those limits, an alarm is generated.
Trends—Built-in trends exist for many of the inputs and outputs for the TEC3000. These trends are viewable at
the TEC. The analog graph displays data in 15-minute increments over the previous 24 hours or a table with
the last 25 data points. Binary trends display 25 samples taken at every change of state.

Menus and submenus

In Figure 13, the * indicates that the menus depend on your configuration.
Table 13: Menus and submenus (Part 1 of 6)
Level 1
Setpoints
Scheduling
TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with
Level 2
(LCD screen name)
Occupied Cooling
Occupied Heating
Unoccupied Cooling
Unoccupied Heating
Standby Cooling
Standby Heating
Dehumidification*
Occ Setpoint Select
Heat Cool Setpoint Mode
Max Heating Setpoint*
Min Heating Setpoint*
Max Cooling Setpoint*
Min Cooling Setpoint*
Max Setpoint*
Min Setpoint*
Schedule Options
Set Schedule
Optimal Start Enable
Temp Occ Duration
Motion Sensor Timeout
Manual Occupancy Mode
Schedule Source
Dehumidification Capability Installation Guide
37