Setting The Control Mode - Johnson Controls TEC3322-1 Series Installation Manual

Networked and wireless proportional fan coil and individual zone thermostat controllers with dehumidification capability
Hide thumbs Also See for TEC3322-1 Series:
Table of Contents

Advertisement

4. Press Supply Fan.
5. Press Supply Fan Type and select Single Speed, Multi-Speed, or Variable Speed.
6. Press Save and the back arrow to return to the previous screen.
For multi-speed fan control, you can adjust the point when the medium or high speed turns on. The fan speed is
based on the load of the cooling/heating device, and is a percentage between 0 and 100. By default, the Med
Speed On Cmd is 33% and the High Speed On Cmd is 66%. When only two fan speeds are used, you must set the
High Speed On Cmd to 100% to disable the third speed. To adjust these values:
1. Press the Menu icon.
2. Press Setup.
3. Press Equipment Setup.
4. Press Supply Fan.
5. Press Medium Speed On Cmd and adjust accordingly.
6. Press High Speed On Cmd and adjust accordingly.
7. Press Save and the back arrow to return to the previous screen.
For VSF control, the output is configurable for any range between 0 V and 10 V. The parameters are Start Voltage,
Full Speed Voltage, and Minimum Command. Start Voltage is the voltage output at which the fan begins running,
and Full Speed Voltage is the voltage output at which the fan reaches full speed. Minimum Command is the
percentage of the range between the Start Voltage and the Full Speed Voltage. The fan does not go below the
minimum command when the fan is turned on. By default, the Start Voltage is 2 V, the Full Speed Voltage is 10 V,
and the Minimum Command is 20%.
When the variable speed fan is off, the FAN binary output is off and the voltage at the VSF output is 0 V. When the
fan turns on, the FAN binary output turns on and the voltage at the VSF output begins controlling the fan. When the
VSF is configured for reverse acting mode, when the Start Voltage is above Full Speed Voltage, the VSF output is
set to 10 V or the Start Voltage minus 1 V, whichever value is the lesser, when the fan is turned off.
To configure the variable speed parameters:
1. Press the Menu icon.
2. Press Setup.
3. Press Equipment Setup.
4. Press Supply Fan.
5. Press Start Voltage and adjust accordingly.
6. Press Full Speed Voltage and adjust accordingly.
7. Press Minimum Command and adjust accordingly.
8. Press Save and the back arrow to return to the previous screen.

Setting the Control mode

The Control Mode informs the controller to run in Cooling only, Heating only, or Automatic mode, based on the
temperature in the zone relative to the heating and cooling setpoints. Control Mode does not override equipment
lockouts or changeover. To set the Control Mode:
1. Press the Menu icon.
2. Press Setup.
3. Press General Control Setup.
4. Press Control Mode and select Cooling, Heating, or Auto as desired.
5. Press Save and the back arrow to return to the previous screen.
TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability Installation Guide
23