Aux Control - Johnson Controls TEC3322-1 Series Installation Manual

Networked and wireless proportional fan coil and individual zone thermostat controllers with dehumidification capability
Hide thumbs Also See for TEC3322-1 Series:
Table of Contents

Advertisement

The polarity of the inputs are provided in Table 11.
Table 11: Input polarities
BI configuration
Occupancy
Temp Occ
Motion NO
Motion NC
Dirty Filter
Service
Fan Lock
Open Door
Open Window
Supply Fan Status
Configurations that support both BIs configured for the same feature of the action that occurs when either of
1.
the BIs enter that state.

Aux control

The TEC has an auxiliary output that can be configured to operate in a few different ways. The Aux Mode supports
the following options:
Not Used—Output is always off
Occupied NO—Output is normally open, but closes when occupied
Occupied NC—Output is normally closed, but opens when occupied
Occupied Fan NO—Output is normally open, but is closed when occupied with the fan running
Occupied Fan NC—Output is normally closed, but is open when occupied with the fan running
On—Output is turned on (relay closed), used by a BAS to directly control the AUX output
Off—Output is turned off (relay open), used by a BAS to directly control the AUX output
To set the Aux Mode:
1. Press the Menu icon.
2. Press Setup.
3. Press General Control Setup.
4. Press Aux Mode and set accordingly.
5. Press Save and the back arrow to return to the previous screen.
This option is also exposed to the BAS through the point AUX-MODE.
When the Reheat installed parameter is set to True, the Aux output is used for Reheat Output. The setting for the
Aux Mode is ignored when reheat is enabled.
TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with
Contact open
Unoccupied
No Trigger Active
No Motion Detected, Standby
Motion Detected, Occupied
Dirty Filter Alarm Inactive
Service Alarm Inactive
No Airflow
Door Open, Unoccupied
Window Open, Control Shut Down
Supply Fan Off
Dehumidification Capability Installation Guide
Contact closed
Occupied
Temporary Occupancy Trigger
Motion Detected, Occupied
1
No Motion Detected, Standby
Dirty Filter Alarm
Service Alarm
Airflow
Door Closed, Occupied
Window Closed, Control Running
Supply Fan On
34
1
1
1
1