Appendix 4
The link special register (SW) stores the information during data link as a numerical value. Faulty areas and causes can be
checked by using or monitoring the link special register (SW) in programs.
Application of link special register (SW)
By using link special register (SW), the status of CC-Link IE TSN can be checked from HMI (Human Machine Interfaces) as
well as the engineering tool.
Range where data is stored by users and range where data is stored by the system
The following ranges correspond to when the link special register areas (SW) are assigned from SW0000 to SW0FFF.
• Stored by users: SW0000 to SW001F
• Stored by the system: SW0020 to SW0FFF
List of link special register (SW)
The following table lists the link special register areas (SW) when they are assigned from SW0000 to SW0FFF.
Do not write any data to an area whose No. is not on the following list or ranges where data is stored by the
system. Doing so may cause malfunction of the programmable controller system.
: Available, : Not available
No.
Name
SW001A
REMFR/REMTO
instruction resend
count
SW001B
REMFR/REMTO
instruction response
wait timer time
SW0030
Link dedicated
instructions
processing result
CH1
SW0031
Link dedicated
instructions
processing result
CH2
SW0040
Network No.
SW0042
Station No.
SW0043
Mode status of own
station
APPX
254

Appendix 4 List of Link Special Register (SW)

List of Link Special Register (SW)
Description
Set the number of resends for the REMFR/REMTO/REMFRD/REMTOD instruction.
0: Not resent (default)
Other than the above: Number of times that is set, 1 to 15 (times)
Set the response wait time for the REMFR/REMTO/REMFRD/REMTOD instruction.
0: 10 seconds (default)
Other than the above: Number of seconds that is set, 1 to 32767 (seconds)
Stores the processing results of the link dedicated instruction that used channel 1 of the
own station.
0: Completed successfully
1 or greater: Completed with an error (Error code is stored.)
Stores the processing results of the link dedicated instruction that used channel 2 of the
own station.
0: Completed successfully
1 or greater: Completed with an error (Error code is stored.)
Stores the network No. of the own station.
Range: 1 to 239
Stores the station No. of the own station.
Range:
• Master station: 125
• Local station: 1 to 120, 255 (station number not set)
Stores the module operation mode setting or communication mode of the own station.
0: Online mode/Unicast mode
1: Online mode/Multicast mode
2: Offline mode
B: Module communication test mode
Availability
PLCopen
Simple
Motion
Motion
control FB
mode
mode