Security

Set the security measures for access to the Ethernet device.
Item
IP Filter
IP Filter
Settings
IP Filter Settings
IP Filter Settings
Up to 32 IP addresses can be set as an IP address to be allowed or denied by the IP filter.
Range specification and specification of the IP addresses to be excluded from the set range as a single setting are possible.
Item
Access from IP address below
Range Setting
IP Address
IP Address Excluded from Range

Interlink Transmission Settings

Set link device ranges when cyclic data are transferred from a station in the own network to a station in a different network.
For details of interlink transmission settings, refer to "Parameter setting" in the following manual.
MELSEC iQ-R CC-Link IE TSN User's Manual (Application)
Precautions
• The value transferred for RY/RWw assigned to the motion control station is not reflected in the output to the motion control
station. Additonally, when operating in multicast mode, the value transferred to RY/RWw assigned to the motion control
station is not stored in the local station link device (RX/RWr).
• When setting the Motion module RX/RWr to the transfer origin, the value (initial value 0) written last is transferred to the RX/
RWr assigned to the motion control station by direct access, etc. of the link device.
When the version of Add-on baseSystem is "1.22" or earlier, the Motion module will operate without any
setting when interlink transmission is set.
Description
Set whether to use the IP filter.
Set the IP addresses to be allowed or denied.
Description
Select whether to allow or deny the access from the specified IP addresses.
Select this item when specifying the IP addresses by range.
Set the IP addresses to be allowed or denied.
When selecting "Range Setting", enter the start IP address (left field) and end IP address
(right field) of the range.
When selecting "Range Setting", set the IP address to be excluded from the set range.
Up to 32 IP addresses can be set.
Setting range
• Not Use
• Use
(Default: Not Use)
Setting range
• Allow
• Deny
(Default: Allow)
(Default: Clear)
0.0.0.1 to
223.255.255.254
(Default: empty)
0.0.0.1 to
223.255.255.254
(Default: empty)
2 PARAMETER SETTINGS