Check

6. Check

6.1

How to Check

6.1.1 Fan Motor Connector Output Check
Check No.01
1. Check the connection of connector.
2. Check motor power supply voltage output (pins 4 - 7).
3. Check motor control voltage (pins 4 - 3).
4. Check rotation command voltage output (pins 4 - 2).
5. Check rotation pulse input (pins 4 - 1).
149
S1
7
Motor power supply voltage (310 ~ 340 VDC)
6
Unused
5
Unused
4
GND
3
Motor control voltage (15 VDC)
2
Rotation command voltage (1~ 5 VDC)
1
Rotation pulse input
SiUS12-928_A
(R12404)