Chapter 12 - Standard Modbus Read, Write and Override Parameters
Parameter Description
Alarm Status Register Map
Table 12-11: Alarm Status
Parameter Description
Alarm Status #1 ~ #16
Alarm Set Point Value Register Map
Table 12-12: Alarm Set Point Value Register Map
Parameter
Description
Alarm Set Point Value
1
Alarm Set Point Value
2
Alarm Set Point Value
3
Alarm Set Point Value
4
393
Register Address
Hex
Decimal
Register Address
Hex
Decimal
1BF0
47153
Register Address
Hex
Decimal
1C00
47169
1C02
47171
1C04
47173
1C06
47175
Access
Description
clear an infinite shed
condition. (Shed time =
0) Data is ignored.
Access
Description
R
Bit Packed:
Bit 0: Alarm #1 Status
Bit 15: Alarm #16 Status
0: Alarm OFF
1: Alarm ON
Access
Description
R/W
Floating Point in Engineering
Units.
R/W
Floating Point in Engineering
Units.
R/W
Floating Point in Engineering
Units.
R/W
Floating Point in Engineering
Units.
⁞