Communications Group - Honeywell UDC2800 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2800:
Table of Contents

Advertisement

Communications Group

Introduction
The Communications group lets you configure the controller with
Easyset, a mobile app that communicates through Bluetooth, and
lets a Modbus® client/master host communicate with the controller
via Ethernet TCP/IP protocol.
A controller with the Ethernet option looks for messages from the
host computer. If these messages are not received within the
configured shed time, the controller will SHED from the
communications link and return to stand-alone operation. You can
also set the SHED output mode and setpoint recall, and
communication units.
Up to 99 addresses can be configured over this link. The number of
units that can be configured depends on the link length, with 31
being the maximum for short link lengths and 15 drops being the
maximum at the maximum link length.
Function Prompts
Table 4-14: Communications Group Function Prompts
Selections or
Function
Range of
Prompt
Setting
Bluetooth
Disable
Function
Enable
Bluetooth ID
UXXXXXXXX
Bluetooth
XX:XX:XX:XX:XX
Mac Address
:XX
Communicati
on Type
Disable
Modbus
Parameter Definition
Disables/enables the Bluetooth function.
Read only. It is an ID that is assigned to a controller
that is to be used with the communications option.
Read only.
Communication type selection - enables the RS485
or Ethernet communication port.
Disable —Disables communications option.
Modbus —Enables RS485 Modbus RTU
communication port.
Chapter 4 - Configuration
148

Advertisement

Table of Contents
loading