Chapter 7 - Output Calibration
Table 7-6: Restore Factory Calibration
Step
Operation
1
Select Lockout
to None
2
Enter Output
or Options set
up Group
3
Scroll through
Functions
4
Return to
Normal
251
Press
Result
Setup key
Until you see Security.
Function key
Enter into the first function prompt
Password of the Security set up group.
Press the Function key again to enter the
correct password.
Function key
You can see Lockout appears. Press the
Function key again to enter into the
configuration prompt of the Lockout.
Increment key or
Until you see None.
Decrement key
Function key
Set Lockout to None.
Setup key
Until you see Output or Options.
Output is for the Current Output, and
Options is for the Auxiliary Output.
Function key
Enter into the first function prompt of the
Output or Options set up group.
Increment key or
Until you see CO Range.
Decrement key
Function key
Enter into the first configuration prompt of
the Output or Options set up group.
Increment key or
To change the range configuration to the
Decrement key
other selection
Function key
Until the lower display rolls through the
rest of the functions and returns to Co
Range.
Increment key or
To change the range selection in the upper
Decrement key
display back to the proper selection.
Lower Display
Return to Normal operating mode.
key
ATTENTION: Users must be careful
while entering the password as the
password is not hidden.