Honeywell UDC2800 Product Manual page 239

Universal digital controller
Hide thumbs Also See for UDC2800:
Table of Contents

Advertisement

Chapter 6 - Input Calibration
Step
Operation
2
Enter Input
set up
group
3
Scroll
through
Functions
4
Return to
Normal
Operation
239
Press
Result
Setup key
Until you see Input N (N=1 or 2).
Function
Enter into the first function prompt Input N Type of
key
the Input set up group. N=1 or 2.
Press the Function key again to enter into the
configuration prompt of Input N Type.
Increment
To change the current selection to another
key or
selection.
Decrement
key
Function
until the lower display rolls through the rest of the
key
functions and returns to Input N Type (N = 1 or 2)
Increment
until you change the input selection back to the
key or
proper selection.
Decrement
key
Lower
return to Normal operating mode.
Display key
The factory calibration will be restored. If the
problem is not corrected, contact your Honeywell
representative.