Chapter 5 - Monitoring and Operating the Controller
Function
Disable
Program
225
Press
Result
in the program or goes into manual mode/failsafe
output, depending upon the "Program Termination"
configuration.
See SP Ramp/Program Set Up Group for more
information.
Power outage
ATTENTION: If power is lost during a program, upon power-up
the controller will be in hold and the setpoint value will be the
setpoint value prior to the beginning of the setpoint program.
The program is placed in hold at the beginning. The mode will
be as configured under "Power Up Mode" in the "Control" set
up group.
Digital input (remote switch) operation
Program can be placed in Run, Hold, Rerun, or To Begin state
through a remote dry contact connected to optional digital input
terminals, as follows:
Run —contact closure places Program in RUN state, OR
Hold —contact closure places Program in HOLD state
Rerun —contact closure allows the Setpoint Programmer to be reset
to the initial segment of its current cycle, unit stays in previous mode.
Opening the contact will cause the Controller to revert to its original
state.
To Begin — Contact closure resets SP Program back to the beginning
of the first segment in the program and places the program in the
HOLD mode. Program cycle number is not affected. Reopening
switch has no effect.
Opening the contact will cause the Controller to revert to its original
state.