Configuration

3.12 Communications Set Up Group

If your controller does not have this option, the prompts will not appear.

Table 3-11 Communications Group Function Prompts

Function
Prompt
Lower Display
ComSTATE
Communications Option
State
Com ADDR
Communications Station
Address
SHEDENAB
Shed Enable
SHEDTIME
Shed Time
PARITY
Parity
Baud Rate
BAUD
Duplex Operation
DUPLEX
34
Function
Name
UDC3300 Basic Model: DC33XB User Manual
Selections or
Range of Setting
Upper Display
DISABL
MODBUS
MB3K
RS422
1 to 99
DISABL
ENABL
0 to 255 sample periods
(1 sample period = 0.333
seconds)
0 = No Shed
NONE
ODD
EVEN
Fixed at NONE when ComSTATE
= MODBUS
2400
4800
9600
19200
HALF
FULL
ATTENTION
• When ComSTATE =
MODBUS, this selection is
fixed at HALF.
• When the RS422/485/Auxiliary
output option board is installed,
this selection is fixed at HALF.
Factory
Setting
DISABL
0
DISABL
0
ODD
2400
HALF
12/00