Section 3-1: Converting Top/Rear Vent - Montigo DelRay Square DRSQ34NI Installation & Maintenance Manual

Indoor direct vent gas fireplace
Table of Contents

Advertisement

Montigo supplies a variety of direct venting and termination options.
The direct vent termination location MUST be selected such that it is the
highest point in the venting assembly. It should also be selected such
that it provides the shortest vent run possible. Should it be impossible
to ensure that the termination is the highest point or to meet the
venting guidelines laid out below please contact your Montigo dealer
to discuss power venting options.
Notes For Planning Venting:
• Venting can originate from the unit through the top or through the rear
• Venting can terminate through the roof or through an exterior wall.
• Refer to Appendix A - Termination Locations to ensure the planned
termination location is acceptable.
• Once the termination location has been established, refer to the
appropriate section below for installation details
• All fireplaces shipped from the factory are top vent.
• Silicone application is NOT required when joining Montigo vent
pipes and components.
Section 3-1: Converting top/rear vent
• Remove the collar cover on the top of the unit, also remove the full
collar cover from the rear of the unit.
• The 2 collars can be now be unscrewed from the top of the unit. (Note
that certain models are not fastened during shipping, hardware can
be found taped to the flue collar.)
• The 2 blanking disks are now removed from the rear of the unit and
placed in their respective positions on the top of the unit with the
included quad screws.
• The vent collars are now secured to the rear of the unit with the
included hardware, finish by attaching the collar cover.
FULL COLLAR
BLANKING
COVER
DISKS
Figure 7. Flue cover and collar removal and install, Top Vented fireplace.
24
ITEM NO.
1
2
3
4
5
FLUE COLLAR
6
7
8
COLLAR COVER
INTAKE COLLAR
Connection and installation of the vent
components should adhere to the following
guidelines:
• Use any combination of rigid and flex pipe as required and in any
orientation (Male connectors can face in any direction).
• Flex sections may be stretched up to 50% of their total length (e.g.
a 24" section maybe stretched to 36").
• Connect all vent sections using a minimum of three sheet metal
screws on the outer pipe, add three additional screws on the inner
pipe when using flex vent.
• Ensure the pipe ends male to female slide in a minimum of 1 1/2"
of overlap.
• Ensure all horizontal runs are supported with a minimum of 3
supports per 10' of venting.
• When hanging/supporting venting, ensure that 1" clearance is
maintained on sides and bottom of vent runs and 2" above horizontal
vent runs to any combustible material.
• Rigid pipe may be cut less than half way from the FEMALE END ONLY.
• Ensure when cutting sections of rigid pipe to maintain integrity of
internal supports.
• Flex pipe cannot be cut
• Place the springs, supplied with the pipe kit (flex only), between the
outer and inner pipes to keep the pipes separate and avoid any
possible hot spots.
• Montigo recommends the use of a flex section for the first section of
venting connected directly to the fireplace, offering greater flexibility
of installation and absorption of movement.
PART NUMBER
DESCRIPTION
• Firestops must be installed as required by national & local codes.
DRSQ38 - Full Assembly
DRSQ38-4 Collar Assembly
DRSQ38-4 inch for 5 inch hole
• Montigo recommends that all exterior corners and joints be sealed
DRSQ38-7 Collar Assembly
DRSQ38-7 Collar Assembly
DRSQ38044-10
8" Full Collar Lid
with exterior caulking. However, we encourage you to consult your
DRSQ38076-10
7" Collar Lid for 8" hole
Building Envelope Engineer or Waterproofing Consultant for further
H42118
8" BLANKING DISK
recommendations.
H42119-10
5" BLANKING PLATE
HW2059
10-24-0.5" RHW Screw Pltd
IMPORTANT:
Please refer to your Building Envelope Engineer
or Waterproofing Consultant for a review of ALL
penetrations through exterior walls or the roof.
Installation
QTY.
1
1
1
1
1
1
1
9
XG0230 - 052020