Drsq34 Rear Venting; 45° Corner Installation 4''/7; 45° Or Less Corner Installation 4''/7 - Montigo DelRay Square DRSQ34NI Installation & Maintenance Manual

Indoor direct vent gas fireplace
Table of Contents

Advertisement

DRSQ34 Rear Venting

A maximum 18" of horizontal run is allowed on rear vented applications ,
though the addition of a 45° elbow is permitted for corner installations.
18'' Max. horozontal
run with no vertical lift
Hearth
Figure 9.b Straight run, Rear Vented, wall mounted termination.
45° Corner Installation 4''/7''
Attach an EEL45 (45° elbow) directly onto the flue collar and attach it
to the EEL45, cut the EXT18 to suit. Slide the fireplace into position and
attach to the termination.
NOTICE
Corner Installation is available for NATURAL GAS UNITS ONLY
16
EXT18 Extention
Heat Sheild
Termination
18''
Max.
251/16''
Termination
RHS 100 (4"/7")
Heat Sheild
EXT18 (4"/7")
EEL45 Elbow (4"/7")
Flue Collar
45° or less Corner Installation 4''/7''
Use an MTO-4 termination and an MFL-1 or MFL-1/MFL-2 (12" or 24"
compressed length) and a frame, if appropriate. Flex may be turned
to obtain desired degree of angle required but must not exceed 45°.
MVK05 kit can be also be used
NOTE: The MVK05 / MVK05F kit is available for top vent corner FLEX
application (NG only). The Kit includes a heat shield, flex pipe, and a
termination with or without a mounting frame.
Installation
DRSQ
34
Termination
RHS 100 (4"/7")
Heat Sheild
Flex Section
Flue Collar
XG0230 - 052020