MQ Power WHISPERWATT Series Operation Manual page 21

Hide thumbs Also See for WHISPERWATT Series:
Table of Contents

Advertisement

120-Volt AC GFCI Receptacles
NOTICE
It is recommended that the GFCI receptacles be tested
when the generator is initially uncrated. The receptacles
should then be tested daily at startup.
There are two 120-volt, 20-amp GFCI (duplex NEMA
5-20R) receptacles provided on the output terminal panel.
These receptacles can be accessed in any voltage selector
switch position. Each receptacle is protected by a 20-amp
circuit breaker. These breakers are located directly above
the GFCI receptacles. Remember that the load output
(current) of both GFCI receptacles is dependent on the
load requirements of the U, V, and W output terminal lugs.
Press the Reset button (Figure 7) to reset the GFCI
receptacle after it has been tripped. Press the Test button
in the center of the receptacle to check the GFCI function.
Both receptacles should be tested at least once a month.
Reference the maintenance section in this manual for
further testing of the GFCI receptacle.
RESET
BUTTON
STATUS
LED
Figure 7. 120-Volt GFCI Receptacle
DCA40SSKU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #2 (08/30/22) — PAGE 21
OUTPUT TERMINAL PANEL FAMILIARIZATION
TEST
BUTTON
Twist-Lock Dual-Voltage 240/120 VAC Receptacles
There are two 240/120V, 50-amp, auxiliary twist-lock
(CS-6369) receptacles (Figure 8) provided on the
output terminal panel. These receptacles can only be
accessed when the voltage selector switch is placed in the
single-phase 240/120V position.
Figure 8. 240/120V Twist-Lock Auxiliary
Receptacles
Each auxiliary receptacle is protected by a 50-amp circuit
breaker. These breakers are located directly above the
GFCI receptacles. Remember the load output (current) on
both receptacles is dependent on the load requirements of
the output terminal lugs.
Removing the Plastic Face Plate
(Hard Wire Hookup Panel)
The Output Terminal Lugs are protected by a plastic face
plate cover (Figure 9). Unscrew the securing bolts and lift
the plastic terminal cover to gain access to the terminal
enclosure.
After the load wires have been securely attached to the
terminal lugs, reinstall the plastic face plate.
PLASTIC
TERMINAL
COVER
SECURING
Figure 9. Plastic Face Plate
(Output Terminal Lugs)
HARD WIRE
HOOKUP PANEL
BOLTS

Advertisement

Table of Contents
loading

This manual is also suitable for:

Whisperwatt dca40ssku4f2

Table of Contents