MQ Power WHISPERWATT Series Operation Manual page 45

Hide thumbs Also See for WHISPERWATT Series:
Table of Contents

Advertisement

3. Verify that the status LED on the corresponding GFCI
receptacle (Figure 70) is ON (GREEN).
Figure 70. GFCI Receptacle (ON)
4. Press the TEST button (Figure 71) on the GFCI
receptacle and verify that the status LED turns OFF.
Figure 71. GFCI Receptacle (OFF)
5. Press the RESET button (Figure 72) to restore power
to the GFCI receptacle and verify that the status LED
is ON (GREEN).
Figure 72. GFCI Receptacle (ON/Restore)
DCA40SSKU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #2 (08/30/22) — PAGE 45
GREEN
STATUS
LED (
ON
)
TEST
BUTTON
STATUS
LED (OFF)
RESET
BUTTON
GREEN
STATUS
LED (ON)
6. If the status LED (Figure 73) is flashing (RED),
DO NOT use the GFCI receptacle. Replace it
immediately.
Figure 73. GFCI Receptacle (Red Flashing LED)
7. Repeat the above procedure for all other GFCI
receptacles.
GENERATOR STORAGE
For long-term storage of the generator the following is
recommended:
„ Drain the fuel tank completely. Treat with a fuel stabilizer
if necessary.
„ Completely drain the oil from the crankcase and refill if
necessary with fresh oil.
„ Clean the entire generator, internal and external.
„ Cover the generator and store in a clean, dry place.
„ Disconnect the battery.
„ Make sure engine coolant is at the proper level.
„ If the generator is mounted on a trailer, jack the trailer
up and place it on blocks so the tires do not touch the
ground, or block and completely remove the tires.
MAINTENANCE
RED
STATUS LED
(
FLASHING
)