GENERATOR OUTPUT VOLTAGES
A wide range of voltages (Table 7) is available for many
different applications.
Table 7. Voltages Available
UVWO Output
Voltage Selector Switch
Terminal Lugs
3-Phase 240/139V Position
208V
3Ø Line-Line
1Ø Line-Neutral
120V
Voltage Selector Switch Single-Phase 240/120V Position
1Ø Line-Neutral/
120V
Line-Neutral
Line-Line
Voltage Selector Switch
Voltages are selected by using the voltage selector switch
(Figure 12) which is located above the output terminal
panel's Hard Wire Hook-Up Panel. This switch has been
provided for ease of voltage selection.
3 PHASE
480/277
PRESS TO LOCK
Figure 12. Voltage Selector Switch
CAUTION
NEVER change the position of the voltage selector
switch while the engine is running. ALWAYS place
the circuit breaker in the OFF position before selecting
voltage.
Voltage Regulator
To obtain some of the voltages listed in Table 7 will require
a fine adjustment using the voltage regulator (VR) control
knob located on the control panel.
DECREASE
Figure 13. Voltage Regulator Control Knob
PAGE 24 — DCA40SSKU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #2 (08/30/22)
Voltage Selector Switch
3-Phase 480/277V Position
220V
240V
416V
440V
127V
139V
240V
254V
240V
N/A
N/A
N/A
Line-Line
3 PHASE
240/139
1 PHASE
240/120
INCREASE

GENERATOR OUTPUTS

MAXIMUM AMPS
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
Table 8. Generator Maximum Amps
Rated Voltage
1Ø 120 volts
480V
277V
1Ø 240 volts
3Ø 240 volts
N/A
3Ø 480 volts
Main Line Circuit Breaker Rating
Over Current Relay Trip Set Point
480V Mode Only
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the three twist-lock auxiliary receptacles.
Figure 17, Table 9 and Table 10 show what amount of
current is available at the GFCI receptacles when the output
terminals and twist-lock receptacles are in use. Be careful
that your load does not exceed the available current
capability at the receptacles.
Table 9. 1Ø GFCI Receptacle Load Capacity
Twist Lock (CS6369)
Table 10. 3Ø Generator Maximum Amps
(UVWO Terminals)
Maximum Amps
80 amps (4 wire)
108A × 2 (zigzag)
40 amps (4 wire)
108A (zigzag)
kW in Use
Available Load
Current (Amps)
GFCI Duplex
1Ø 240/120V
5-20R 120V
26.0
0 amps/receptacle
24.8
5 amps/receptacle
23.6
10 amps/receptacle
22.4
15 amps/receptacle
21.2
20 amps/receptacle
kVA in Use
Available Load
Current (Amps)
GFCI Duplex
3Ø 240/480V
5-20R 120V
36.0
0 amps/receptacle
31.8
5 amps/receptacle
27.7
10 amps/receptacle
23.5
15 amps/receptacle
19.4
20 amps/receptacle
86 amps
43 amps
110 amps
43 Amps