Certification
Section 6.4

EMI and Environmental Type Tests

The RP110 has passed the following EMI and environmental tests.
IEC 61850-3 Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
20
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and Interrupts
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC Power Supply
Dielectric Strength
Enclosure
Contact
Enclosure Air
Enclosure ports
Signal ports
+/- 4 kV @ 2.5 kHz
DC Power ports
AC Power ports
Earth
ground ports
Signal ports
+/- 4kV line-to-earth
DC Power ports
+/- 2kV line-to-earth,
AC Power ports
+/- 4kV line-to-earth,
Signal ports
D.C Power ports
AC Power ports
Earth
ground ports
Enclosure ports
40 A/m continuous, 1000 A/m for 1 s
DC Power ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
AC Power ports
30% for 1 period, 60% for 50 periods
100% for 5 periods,
100% for 50 periods
Signal ports
DC Power ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
AC Power ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
Signal ports
30 V Continuous, 300 V for 1 s
DC Power ports
30 V Continuous, 300 V for 1 s
DC Power ports
DC Power ports
Test Levels
+/- 8 kV
+/- 15 kV
20 V/m
a
+/- 4kV
+/- 4kV
+/- 4kV
a
+/- 1kV line-to-line
+/- 2kV line-to-line
10V
10V
10V
10V
a
2.5 kV common
10%
1.5 kVDC
EMI and Environmental Type Tests
RUGGEDCOM RP110
Installation Guide
Severity Levels
4
4
x
x
4
4
4
4
3
4
3
3
3
3
3
3
3
4
4
3

Advertisement