Samsung MWR-WW10JN User Manual page 38

Air to water heat pump wired remote controller
Hide thumbs Also See for MWR-WW10JN:
Table of Contents

Advertisement

Field setting mode
Mixing vavle Installation (Field Option)
The FSV #4041 should be set to "1 or 2" to use mixing valve.
ex) Heating
Tw2
FSV #4042 / #4043 is for adjusting temperature difference between Tw3 (Tw2) and Tw4.
When using mixing valve, FSV #4046 should be matched with mixing valve running time charateristic.
Inverter Pump Installation (Field Option)
FSV #4051=1 (Default) : Inverter pump use + Output 100%, FSV #4051=2 : Inverter pump use + Output
70%, FSV #4051=0 : Inverter pump Not use.
FSV #4052 is for adjusting temperature difference between Tw2 and Tw1.
NOTE
Tw1 (Inlet Water Temp), Tw2 (Discharge Water Temp), Tw3 (Backup Heater oulet Water Temp),
Tw4 (Mixing valve Temp.)
Zone Control (Field Option)
Zone control Using Wired Remote Control (install option) FSV # 4061 should be set to "1 (Yes)" to zone
control.
NOTE
MIM-E03CN (MONO Control Kit) model does not support this zone control function.
English
38
<#4041=1>
FCU WL
#4042
Floor temp
<#4041=2>
Tw2
FCU WL
Floor WL
Ta
Ta