Wired Remote Control
MWR-WW00N

Advertisement

Table of Contents
loading

Summary of Contents for Samsung MWR-WW00N

  • Page 1: Installation Manual

    Wired Remote Control MWR-WW00N DVM Hydro unit / Hydro unit HT installation manual imagine the possibilities Thank you for purchasing this Samsung product. DB68-03973A-06...
  • Page 2: Safety Information

    Safety information This installation manual explains how to install a wired remote controller connected to a Hydro unit/Hydro unit HT. Please read this manual thoroughly before installing the remote controller. (Please refer to the corresponding installation manual for product and other optional installation.) Hazards or unsafe practices that may result in severe personal injury or death.
  • Page 3 CAUTION Do not install the product where imflammable content may leak. f Failure to do so may result in fire and explosion. Ensure no water gets into the wired remote controller. f Failure to do so may result in electric shock and fire. Install the product away from direct exposure to sunlight, in room temperature range of 0°C(32°F)~39°C(102°F).
  • Page 4: External Dimensions

    Wired remote controller installation Accessories Wired remote Installation Name Cable tie Cable clamp M4X16 Screw User Manual U-Terminal controller Manual Quantity Shape • The wired remote controller should be installed by a certified technician. • Check and confirm the power is off before installing your wired remote controller. CAUTION • Install the wired remote controller cables in accordance with the electrical wiring regulation, and allow it to pass through the inner area of the wall so that other people can’t reach it.
  • Page 5 1. Push the two hooks at the bottom of your Wired Remote Controller at the same time, and then pull up the front cover to separate it from the rear cover. ❋ ❋ Push the two hooks at the same time. • Insert a flat head screwdriver into the square groove in the upper area of the hook to disassemble it easily.
  • Page 6 Wired remote controller installation 3. Using more than two screws, firmly affix the rear cover of the remote controller to the wall, and then connect communication cables(F3, F4), making sure these cables have reasonable length, to the terminal at the back of the cover. Hydro unit/Hydro Hydro unit/Hydro unit HT unit HT PCB...
  • Page 7 • When installing a wired remote controller by using a cable longer than 10 m, you must install the communication cable and the power cable separately. (Electrical interference can cause your wired remote CAUTION controller to malfunction.) • When installing your wired remote controller on the wall, consider the size of the wire hole, and select a wire with a proper thickness.
  • Page 8 Wired remote controller installation Tracking Hydro unit/Hydro unit HT from a wired remote controller Display tracking is being performed. The number of Hydro unit/Hydro unit HT currently detected 1. Tracking of your wired remote controller will automatically start when you turn on the power after installation. 2.
  • Page 9 Individual control with your wired remote controller f Individual control means that you are using one remote controller to control one indoor unit or one Hydro unit/Hydro unit HT. When connecting the Hydro unit/Hydro unit HT only Outdoor unit COM1(F1, F2) COM1(F1, F2) Hydro Hydro...
  • Page 10 Wired remote controller installation Group control with your wired remote controller f Group control means that you are using one wired remote controller to control two or more Hydro unit/Hydro unit HTs at the same time. When connecting the Hydro unit/Hydro unit HT only 1) Using one wired remote controller to control three Hydro unit/Hydro unit HTs Outdoor unit COM1(F1, F2)
  • Page 11 Controlling 2-remote controller f 2-Remote controller is controlling one Hydro unit/Hydro unit HT with two remote controllers. f When setting the wired remote controller as ‘Indoor temperature standard/wired remote controller sensor use’ , please install the master remote controller at indoor places. Outdoor unit COM1(F1, F2) Hydro...
  • Page 12 Wired remote controller installation Sharing the temperature of hot water tank sensor Connecting one wired remote controller Hot water tank sensor Outdoor unit Hot water tank COM1(F1, F2) COM1(F1, F2) COM1(F1, F2) Hydro Hydro Hydro unit/ unit/ unit/ Unit No. 1 Unit No.
  • Page 13 Connecting 2 or more wired remote controller Hot water tank sensor Outdoor unit Hot water tank COM1(F1, F2) COM1(F1, F2) COM1(F1, F2) Hydro Hydro Hydro unit/ unit/ unit/ Unit No. 1 Unit No. 2 Unit No. 3 Hydro Hydro Hydro unit HT unit HT unit HT...
  • Page 14 Wired remote controller installation Initializing your wired remote controller communication 1. Press the Esc and Delete buttons at the same time for more than 5 seconds. f The communication of your wired remote controller will be initialized, and the device will search for the Hydro unit/Hydro unit HT connected to your wired remote controller again.
  • Page 15 2) Outdoor unit error f The address of Error, “Ao” and error code will be displayed alternately on the remote controller display. 3) Wired remote controller error f The error code will blink at 0.5 second interval on the remote controller display and the address of error will not be displayed.
  • Page 16 Use of wired remote controller installation / service mode Use of installation/service mode SEG Used Sub-menu Main menu 1 2 3 4 1. If you want to use the installation/service mode for your wired remote controller, press the Set and ESC buttons at the same time for more than 3 seconds.
  • Page 17 Installation/Service mode • 'NONE' will be displayed for the menu that setting modes don't support. In some cases, the setting may not be possible or it may not be applied though it is set on the unit. NOTE • If communication initialization is needed after saving the setting, the system will reset automatically and communication will be initialized.
  • Page 18 Use of wired remote controller Use of user setting mode SEG Used Sub-menu Main menu 1 2 3 4 1. If you want to use the various user setting modes for your wired remote controller, press the User Set button. 2.
  • Page 19 User setting mode • 'NONE' will be displayed for the menu that setting modes don't support. In some cases, the setting may not be possible or it may not be applied though it is set on the unit. NOTE • If communication initialization is needed after saving the setting, the system will reset automatically and communication will be initialized.
  • Page 20 Field specification setting mode of wired remote controller Use of field specification setting mode Data Main menu Sub-menu 1. If you want to use the field specification setting mode for your wired remote controller, press the Set and [∨] buttons at the same time for more than 3 seconds. 2.
  • Page 21 Field specification setting mode 1. Hydro unit Code (Main Classification Function Detail Basic Min. Max. Step Unit + sub menu) Max. 1011 °C Temperature of general cooling leaving water Min. 1012 °C Max. 1021 °C General indoor cooling temperature Min. 1022 °C Remote...
  • Page 22 Field specification setting mode of wired remote controller Code (Main Classification Function Detail Basic Min. Max. Step Unit + sub menu) Heating/hot water 0 (Hot 4011 priority water) (Heating) Heating Heating mode Heating priority 4012 °C Heating Off 4013 °C Temperature of 5011 °C...
  • Page 23 2. Hydro unit HT Code (Main Classification Function Detail Basic Min. Max. Step Unit + sub menu) Max. 1011 °C Temperature of general cooling leaving water Min. 1012 °C Max. 1021 °C General indoor cooling temperature Min. 1022 °C Max. 1031 °C Remote...
  • Page 24 Field specification setting mode of wired remote controller Code (Main Classification Function Detail Basic Min. Max. Step Unit + sub menu) Temperature of cooling 5011 °C water oulet Room Temperature of 5012 °C cooling Mode Temperature of heating 5013 °C leaving water Indoor heating Outing mode...
  • Page 25 f Code: 20** #2021 or #2031 #2022 or #2032 #2011 #2012 Target water temperature Ambient (outdoor) temperatur 1) In case of outdoor temperature (Ta)°C < (Code #2011)°C - Code #2041: 1 (Floor) Setting Ts = #2021 - Code #2041: Setting 2 (Fan Coil Unit) Ts = #2031 2) In case of (Code #2011)°C ≤...
  • Page 26 Field specification setting mode of wired remote controller • 3041: Application of disinfection function • 3042: Scheduling (day) Sunday Monday Tuesday Wednesday Thursday Friday Saturday AllDay • 3043: Starting time (hour) • 3044: Target tank temp • 3045: Duration time (After reaching the target temperature) • 3046: Maximum duration of disinfection operation (disinfection operation stops after the specified duration) ❋...
  • Page 27 Use of field specification checking mode Data Main menu Sub-menu 1. If you want to use the field specification checking mode for your wired remote controller, press the Set and [∧] buttons at the same time for more than 3 seconds. 2.
  • Page 28 Self-test mode of wired remote controller Use of self-test mode 1. You can use the self-test mode when you set the 'self-test entering' as 'Yes' in the installation/service mode. f Select main menu 1  sub-menu 2 in the installation / service mode. 2.
  • Page 29 f Thermostat 1, 2, and solar heat panel are displayed as below when you set them with an indoor unit. Thermostat 1 (Zone 1), Thermostat 2 (Zone 2), Solar heat panel (ON/OFF) f Timer button: Whenever you press the button, the sensor value will be displayed in order. Tw1(In)sensor Tw2(Out1)sensor TW3(Out2) sensor...