Samsung MWR-WW00 Installation Manual
Hide thumbs Also See for MWR-WW00:

Advertisement

Quick Links

DVM Hydro Unit_MWR-WW00_IM_EN_03647A(1).indd 26
2013-01-09 오후 2:48:45

Advertisement

Table of Contents
loading

Summary of Contents for Samsung MWR-WW00

  • Page 1 DVM Hydro Unit_MWR-WW00_IM_EN_03647A(1).indd 26 2013-01-09 오후 2:48:45...
  • Page 2: Air Conditioner

    Wired Remote Control MWR-WW00 Air Conditioner installation manual imagine the possibilities Thank you for purchasing this Samsung product. To receive more complete service, please register your product at www.samsung.com/register EN ES FR IT PT DE EL RU DB68-03647A(1) DVM Hydro Unit_MWR-WW00_IM_EN_03647A(1).indd 27...
  • Page 3: Safety Information

    Safety Information This installation manual explains how to install a wired remote controller connected to a Hydro Unit. Please read this manual thoroughly before installing the remote controller. (Please refer to the corresponding installation manual for product and other optional installation.) WARNING Hazards or unsafe practices that may result in severe personal injury or death.
  • Page 4 CAUTION Do not install the product where inflammable content may leak. f Failure to do so may result in fire and explosion. Ensure no water gets into the wired remote controller. f Failure to do so may result in electric shock and fire. Install the air conditioner away from direct exposure to sunlight, in room temperature range of 0°C(32°F)~39°C(102°F).
  • Page 5: Wired Remote Controller Installation

    Wired Remote Controller Installation Accessories Installation Wired remote Name Cable tie Cable clamp M4X16 Screw User Manual U-Terminal controller Manual Quantity Shape • The wired remote controller should be installed by a certified technician. • Check and confirm the power is off before installing your wired remote controller. CAUTION • Install the wired remote controller cables in accordance with the electrical wiring regulation, and allow it to pass through the inner area of the wall so that other people can’t reach it.
  • Page 6 1. Push the two hooks at the bottom of your Wired Remote Controller at the same time, and then pull up the front cover to separate it from the rear cover. ❋ Push the two hooks at the same time. • Insert a flat head screwdriver into the square groove in the upper area of the hook to disassemble it easily.
  • Page 7 Wired Remote Controller Installation 3. Using more than two screws, firmly affix the rear cover of the remote controller to the wall, and then connect the power(V1, V2) and communication cables(F3, F4), making sure these cables have reasonable length, to the terminal at the back of the cover.
  • Page 8 • When installing a wired remote controller by using a cable longer than 10m, you must install the communication cable and the power cable separately. (Electrical interference can cause your wired remote CAUTION controller to malfunction.) • When installing your wired remote controller on the wall, consider the size of the wire hole, and select a wire with a proper thickness.
  • Page 9 Wired remote controller installation Tracking Hydro Unit from a wired remote controller Display tracking is being performed. The number of Hydro Unit currently detected 1. Tracking of your wired remote controller will automatically start when you turn on the power after installation. 2.
  • Page 10 Individual control with your wired remote controller f Individual control means that you are using one remote controller to control one indoor unit or one Hydro Unit. When connecting the Hydro Unit only Outdoor unit COM1(F1, F2) COM1(F1, F2) Hydro Hydro Hydro Unit...
  • Page 11 Wired remote controller installation Group control with your wired remote controller f Group control means that you are using one wired remote controller to control two or more Hydro Units at the same time. When connecting the Hydro Unit only 1) Using one wired remote controller to control three Hydro Units Outdoor unit COM1(F1, F2)
  • Page 12 Controlling 2-remote controller f 2-Remote controller is controlling one Hydro Unit with two remote controllers. f When setting the wired remote controller as 'Indoor temperature standard/wired remote controller sensor use' , please install the master remote controller at indoor places. Outdoor unit COM1(F1, F2) Hydro...
  • Page 13 Wired remote controller installation Initializing your wired remote controller communication 1. Press the Esc and Delete buttons at the same time for more than 5 seconds. f The communication of your wired remote controller will be initialized, and the device will search for the Hydro Unit connected to your wired remote controller again.
  • Page 14 Error display on the wired remote controller f Error codes for the wired remote controller and the product connected to your wired remote controller will be displayed in the LCD display. Error indications are displayed as seen below. 1) Hydro Unit error f The address of error(A), "In", and the error code will be displayed alternately on the remote controller display.
  • Page 15 Wired remote controller installation Wired remote controller error code Error codes Take follow actions against those sensor errors f Check sensor resistance at first. - 10 kΩ @ 24˚C(75.2˚F)(Water in of water pipe, water out of water pipe, R-410A EVA inlet, EVA outlet.) f Check the location of a sensor (Refer to 'structure drawing' in the Hydro Unit installation manual) f Check the status of sensor attachment with pipes.
  • Page 16 Data error on remote controller (FRAM read/write error) Error on the sensor of water inlet pipe (Short or Open) Error on the sensor of water outlet pipe(Short or Open) Error on water tank sensor(Short or open) Error due to pipe rupture protection Error due to freeze prevention Water temperature sensor on water outlet pipe is detached Flow switch off error (When the switch is turned off within 10 seconds after a pump starts its operation)
  • Page 17: Use Of Wired Remote Controller Installation / Service Mode

    Use of wired remote controller installation / service mode Use of installation/service mode SEG Used Sub-menu 1 2 3 4 Main menu 1. If you want to use the installation/service mode for your wired remote controller, press the Set and ESC buttons at the same time for more than 3 seconds.
  • Page 18 Installation/Service mode • 'NONE' will be displayed for the menu that setting modes don't support. In some cases, the setting may not be possible or it may not be applied though it is set on the unit. NOTE • If communication initialization is needed after saving the setting, the system will reset automatically and communication will be initialized.
  • Page 19 Use of wired remote controller Use of user setting mode SEG Used Sub-menu 1 2 3 4 Main menu 1. If you want to use the various user setting modes for your wired remote controller, press the User Set button. 2.
  • Page 20 User setting mode • 'NONE' will be displayed for the menu that setting modes don't support. In some cases, the setting may not be possible or it may not be applied though it is set on the unit. NOTE • If communication initialization is needed after saving the setting, the system will reset automatically and communication will be initialized.
  • Page 21: Field Specification Setting Mode Of Wired Remote Controller

    Field specification setting mode of wired remote controller Use of field specification setting mode Main menu Sub-menu Data 1. If you want to use the field specification setting mode for your wired remote controller, press the Set and [∧] buttons at the same time for more than 3 seconds. 2.
  • Page 22 Field specification setting mode Classification Function Detail Code Basic Min. Max. Step Unit 1011 °C Temperature of general cooling discharge water 1012 °C 1021 °C General indoor cooling temperature 1022 °C Remote 1031 °C Temperature of general heating controller discharge water 1032 °C 1041...
  • Page 23 Field specification setting mode of wired remote controller Classification Function Detail Code Basic Min. Max. Step Unit Operation 3031 1 (Yes) 0 (No) Delayed time 3032 Booster heater Overshoot 3033 °C Compensation temperature 3034 °C Operation 3041 1 (Yes) 0 (No) Operation interval 3042 1 (All)
  • Page 24 Use of field specification checking mode Data Address of field specification 1. If you want to use the field specification checking mode for your wired remote controller, press the Set and [∧] buttons at the same time for more than 3 seconds. 2.
  • Page 25: Self-Test Mode Of Wired Remote Controller

    Self-test mode of wired remote controller Use of self-test mode 1. You can use the self-test mode when you set the 'self-test entering' as 'Yes' in the installation/service mode. f Select main menu 1  sub-menu 2 in the installation / service mode. 2.
  • Page 26 f Thermostat 1, 2, and solar heat panel are displayed as below when you set them with an indoor unit. Thermostat 1 (Zone 1), Thermostat 2 (Zone 2), Solar heat panel (ON/OFF) f Timer button: Whenever you press the button, the sensor value will be displayed in order. Tw1(In)sensor Tw2(Out1)sensor TW3(Out2) sensor...