Advertisement

Field setting mode
<Example of using BSH in hot water supply>
(Thermo off / on operation temperature is used together)
[Thermo on/off control of Heat pump and Booster Heater]
#3033
T
OFF
BH OFF
T
ON
BH ON
T
U
T
MAX
HP MAX
#3022
T
OFF
HP OFF
#3023
T
ON
HP ON
HP
Disinfection Function
The FSV #3041 should be set to "1 (On)" (Default) to use disinfection function.
Scheduling : Day (#3042, Default "Friday"), starting time (#3043, Default "23:00"),
[Time variation control of Heat pump and booster heater of DHW]
English
34
BH
HP
t
#3044
T
H
T
U
00.00
01.00
22.00
Thp
OFF
Thp
ON
HP & BH
#3045
23.00
24.00
t
#3043
t