Installation And Application Information - Daikin Clima-Flex CLIV Series Installation, Operation And Maintenance Manual

Air-cooled fixed compressor chilled water chiller unit
Hide thumbs Also See for Clima-Flex CLIV Series:
Table of Contents

Advertisement

Table 1. Limites De Funcionamiento Y Espera
Maximum standby ambient temperature
Maximum operating ambient temperature
Minimum operating ambient temperature (standard control)
Outgoing chilled water temperature
Outgoing chilled fluid temperatures (with antifreeze) - Note that in cases of high ambient temperature,
the lowest outgoing water temperature settings may be outside the chiller operating envelope.
Maximum evaporator inlet fluid temperature
Maximum non-operating evaporator inlet fluid temperature
NAMEPLATES
The unit nameplate is located on the outside of the unit power
panel. Both the model number and serial number are located on
the unit nameplates; the serial number is unique to the unit.
These numbers should be used to identify the unit in case of
service, parts or warranty questions. This nameplate also contains
the unit's refrigerant charge and electrical ratings. The evaporator
nameplate is under the insulation and contains the serial number.
The compressor nameplate is located on each compressor and
provides pertinent electrical information.
!
WARNING
Installation should be performed by qualified personnel who
are familiar with local codes and regulations.
INSPECTION
The equipment must be checked once it has arrived at its
installation site for any damage. All components described in
the delivery note must be inspected and checked. In case there
is evidence of damage, do not remove or repair the damaged
components and immediately report the severity and type of
damage to the shipping company and your sales representative
if possible send photographs that may help explain/detail the
damage.
Any damage detected during transport must be reported and
documented to the manufacturer prior to repair. Before installing
the equipment, check that the model and voltage shown on the
nameplate are correct. The manufacturer will not be responsible
for any damage once the equipment has been accepted.
The correct space dedicated for the maintenance of the equipment
will allow a better installation and maintenance, facilitating the
access to the service points to the technical personnel. Refer
to the schematics presented for unit dimensions. At least one
(1) meter is required to service the compressor, allow sufficient
space for opening control panel doors. Refer to Figure 2 for
minimum clearances. In all cases, these precedents are noted for
any need to comply with local regulations.
iom-cliv-cf-eng

Installation and Application Information

!
6
HANDLING
When transporting the unit, the use of a forklift or crane is
recommended. All units are provided with lifting points. Only
these points should be used for lifting the unit as shown in Fig. 1.
!
CAUTION
All lifting locations must be used to avoid damage to the unit.
!
DANGER
Improper rigging, lifting or moving of a unit can result
in property damage, serious personal injury or death.
Follow the rigging and moving instructions carefully. Do
not stand under the unit while it is being lifted or installed.
Figure 1. Required elevation arrangement.
130°F (54°C)
105°F (41°C)
32°F(0°)
40°F A 65°F (4°C to 18°C)
15°F A 65°F (-9°C to 18°C)
81°F (27°C)
100°F (38°C)
!
!
www.clima-flex.com