Unit Controller Operation
INPUTS AND OUTPUTS
Tabla 6. Analog inputs
Physical address
S1
S2
S3
Tabla 7. Digital inputs
Physical address
ID1
ID2
ID3
ID4
ID5
Tabla 8. Digital outputs
Physical address
NO1
NO2
NO3
NO4
NO5
Output available for alarm connection
SET POINTS
When we start configuring the unit for the first time all the preload parameters have a default value, these values are stored in permanent
memory but can be changed depending on the application of the unit.
Values can be changed from the display and submenus require a password if values are to be changed; if an option is not included in the
display menu the data is only an internal value in the controller and will be visible only if that mode is selected.
Operating parameters:
PARAMETER
U077
S068
U076
C046
C047
S065
S064
Hc31
Hc32
www.clima-flex.com
Electrical diagram label
SR
SI
SC
Electrical diagram label
IF
C/H
AP
BP
System
Electrical diagram label
C1-A2
2-E2
MC-95
B-24V2
VALUE
0
0
0
1
0
0
0
7
8
Name
Return Sensor
Injection Sensor
Condenser Sensor
Name
Flow sensor
Heating / cooling switch
High pressure switch
Low pressure switch
Cliv unit on/off switch
Compressor 1
Compressor 2
Water pump
Hc14
Hc15
Hc06
Hc07
U006
U007
U008
U009
Hc013
25
Name
4-way valve
-
1
2
9
4
5.0
20.0
30.0
45.0
1