Daikin Clima-Flex CLIV Series Installation, Operation And Maintenance Manual page 34

Air-cooled fixed compressor chilled water chiller unit
Hide thumbs Also See for Clima-Flex CLIV Series:
Table of Contents

Advertisement

Alarm
A05
This alarm indicates when the water return sensor or water return probe is damaged or broken.
A06
This alarm indicates when the water injection sensor is damaged or broken.
A10
This alarm indicates when there is a census or water flow problem.
This alarm usually appears together with the A10 alarm as it depends on the configuration at which the pump was com-
A12
missioned, otherwise the current equipment containing this controller simply has a pump configured in this case this
alarm goes together with the current pump configuration.
This alarm usually appears when the water temperature does not drop due to the current cooling process. This alarm is
A15
more of a WARNING than a serious alarm since it is simply an indicator that the equipment is not cooling and therefore
the water temperature is not dropping.
A20
This alarm indicates when the condenser temperature probe is broken or disconnected.
A21
This alarm indicates when the suction temperature sensor is broken or disconnected.
A25
This alarm indicates when the high pressure switch has suffered a change in its signal.
A29
This alarm indicates when the low pressure switch is active.
A49
When the controller has a slave unit this alarm will be present if the slave is disconnected.
iom-cliv-cf-eng
Description
34
Alarms